DISCONNECTING THE BONDED NEUTRAL
Removing the bonded neutral disables the GFCI protection
from the 5-20R receptacles. The bonded neutral should
disconnecting the bonded neutral.
Remove the alternator cover.
Remove the bonded jumper wire and reinstall the nut.
Remove the nut securing the neutral ground wire and
attach the bonded jumper wire. Reinstall the nut.
Reinstall the alternator cover.
IMPORTANT: Apply a new "NEUTRAL UNBONDED"
Label over the "NEUTRAL BONDED TO
FRAME" label on the front of the control
panel.