Three-phase machines are powered with the three-phase + neutral lines: be careful never
to connect the phase lines with neutral. FRIGOMAT will not be held liable for damage to
the machine deriving from incompliance with this rule.
Use of the machine with incorrect beater motor rotation entails the risk of the plastic
impeller detaching from its support, causing breakage of the concerned parts.
• Make sure that the cold water supply line intended
for condensation has pressure values between 1
and 3 BAR (between 100 kPa e 300 kPa) and
temperature between 13° and 20°C.
• Always use new pipes suitable the the IEC 61770
standards.
Never
piping.Use suitable DIN 3017 hose clamps (water
cooling only).
• Connect the cold water supply pipe intended for
condensation onto the machine inlet as shown in
the figure. Use a Ø1/2" fitting and place a gate
valve at the operator's reach.
• Connect the condensation water drain pipe onto
the machine outlet as shown in the figure, using a
Ø1/2" fitting.
• The drain pipe must have an inclination of at least
3 mm for each meter of length.
• After having connected the water inlet and outlet
pipes, with the machine stopped, open the cut-off
cock and make sure that water does not leak from
the drain.
• Turn the general switch off and check the following:
1. Rotation sense of the beter motor
When the unit is on STOP, push the MIXING
key and ensure that the rotation sense of the
disc wheel inside the tank is Clockwise as
shown in the picture (only for 3-phase models):
If the rotation is not clockwise, cut power and
invert the two phases in the plug (only three-
phase models).
use
worn
or
consumed