Using an External Input Signal
When using an externally supplied low voltage signal for external control, input voltage must be within 5-30V AC/DC.
The wiring kit's RED wire is only intended to carry the +24V output signal from the drive and will NOT be used.
The +24V signal (RED wire) is output from the drive only and should never be wired to another power supply. Improper wiring
will damage the drive.
The external output signal can be regulated by switches or relays to initiate a desired pump function. If multiple digital
inputs are active, the priority is: QUICK CLEAN > PROGRAM 3 > PROGRAM 2 > PROGRAM 1.
TO WIRE FOR EXTERNAL CONTROL USING AN EXTERNAL INPUT SIGNAL:
1. Route the communication cable from the Pump
Com Port (Figure 5 on page 5) to the control
system wiring compartment.
2. Ensure the cable reaches all necessary terminals
and cut to the necessary length.
3. Strip the cable 3/4" (19 mm).
4. Strip all conductors 1/2" (13 mm).
5. If using Digital Input Wiring Kit (P/N 353129Z
- Almond): Wire communication cable to control
system as shown in Figure 7A.
If using RS-485 Automation Wiring Kit (P/N
356324Z - Black): Wire communication cable to
control system as shown in Figure 7B.
Note: Unused conductors should be cut off
and terminated according to local and national
electrical codes.
6. Using the pump keypad, program the pump's
internal clock. Refer to Setting the Clock and
Pump Address on page 8.
7. Using the pump keypad, set PROGRAM 1 to a
speed of 0 RPM and duration of 24 hours. Refer to Programming Custom Schedules on page 8.
8. Using the pump keypad, disable priming. Refer to Priming Adjustment on page 11.
9. When ready to start the pump, place the pump into External Control Only mode. Refer to External Control Only
Mode.
10. Plug the communication cable into the Pump Com Port.
External Control Only Mode
External Control Only mode will only allow the pump to run from external controls/inputs. When this mode is active
the programmed pump schedule is deactivated, and user speed requests from the keypad will not be accepted. If the
pump is stopped a user can still program the speeds for all four PROGRAM buttons.
Note: The following steps are required if controlling the pump via digital inputs, but
optional if controlling via RS-485. The pump will prioritize RS-485 commands over
digital input commands.
TO ENABLE/DISABLE EXTERNAL CONTROL ONLY MODE:
1. If the pump is running or Start/Stop LED is illuminated, press the Start/Stop button
to stop the pump.
2. Press and hold the Start/Stop button for 10 seconds to enable/disable External
Control Only mode.
The Ext. Control Only LED will illuminate if enabled. See Figure 8.
3. Press the Start/Stop button to start the pump.
WHISPERFLO
Figure 7A
Figure 7B
XF
XF
®
®
VS and MAX-E-PRO
VS Commercial Variable Speed Pump Installation and User' s Guide
Digital Input Wiring Kit
(P/N 353129Z - Almond)
EXTERNAL
LOW VOLTAGE
SUPPLY
(5-30V AC/DC)
RS-485 Automation Kit
(P/N 356324Z - Black)
EXTERNAL
LOW VOLTAGE
SUPPLY
(5-30V AC/DC)
RED
DO NOT USE
GREEN
SPEED 1 DIGITAL INPUT
YELLOW
SPEED 2 DIGITAL INPUT
ORANGE
SPEED 3 DIGITAL INPUT
BROWN
QUICK CLEAN DIGITAL INPUT
BLACK
GROUND
RED
DO NOT USE
YELLOW
NOT USED
GREEN
NOT USED
WHITE
SPEED 1 DIGITAL INPUT
BLUE
SPEED 2 DIGITAL INPUT
ORANGE
SPEED 3 DIGITAL INPUT
BROWN
QUICK CLEAN DIGITAL INPUT
BLACK
GROUND
9 : 00
Pm
Figure 8
7