9. HOW TO INSTALL THE CEILING PANEL
■ 4-Way Air Discharge Semi-Concealed Type
(X Type)
Checking the unit position
GB
(1) Check that the ceiling hole is within this range:
860 × 860 to 910 × 910 mm
(2) Use the full-scale installation diagram (from the
packaging) that was supplied with the unit to
FR
determine the positioning of the unit on the ceiling
surface. If the positions of the ceiling surface and
unit do not match, air leakage, water leakage, flap
operation failure, or other problems may result.
DE
CAUTION
IT
PT
GR
9-1. Before Installing the Ceiling Panel
(1) Remove the air-intake grille and air filter from the
ceiling panel. (Figs. 9-3, 9-4 and 9-5)
ES
a) Remove the 2 screws on the latch of the air-
intake grille. (Fig. 9-3)
b) Slide the air-intake grille catches in the
direction shown by the arrows 1 to open the
grille. (Fig. 9-4)
c) With the air-intake grille opened, remove the
grille hinge from the ceiling panel by sliding it in
the direction shown by the arrow 2.
(Fig. 9-5)
(2) Removing the corner cover
a) Slide the corner cover to the direction shown
by the arrow 1 to remove the corner cover.
(Fig. 9-6)
Corner cover
DC̲Inverter̲Eng.indd 62
DC̲Inverter̲Eng.indd 62
●
Never place the panel
face-down. Either hang
it vertically or place it
on top of a projecting
object. Placing it face-
down will damage the
surface.
●
Do not touch the flap or
apply force to it.
(This may cause flap
malfunction.)
Push
A
must be within the range of 12 – 17 mm.
If not within this range, malfunction or other trouble may result.
A
Ceiling side
Screw
Latch
Fig. 9-3
Air-intake grille hinge
2
Fig. 9-5
Corner cover
1
Strap
Fig. 9-6
62
Main unit
Ceiling opening
dimension
Fig. 9-1
Wing
Fig. 9-2
Air-intake grille
Ceiling panel
1
1
Fig. 9-4
Ceiling panel