2-3. Air Discharge Chamber for Top Discharge

Be sure to install the air discharge chamber in the
field when:
it is difficult to keep a space of min. 50 cm between
the air discharge outlet and an obstacle.
the air discharge outlet is facing a sidewalk and
discharged hot air annoys passers-by.
Refer to Fig. 2-9.

2-4. Installing the Unit in Heavy Snow Areas

In locations with strong wind, snow-proof ducting
should likewise be fitted and direct exposure to the
wind should be avoided as much as possible.
■ Countermeasures against snow and wind
In regions with snow and strong wind, the following
problems may occur when the outdoor unit is not pro-
vided with a platform and snow-proof ducting:
a) The outdoor fan may not run and damage of the
unit may be caused.
b) There may be no air flow.
c) The tubing may freeze and burst.
d) The condenser pressure may drop because of
strong wind, and the indoor unit may freeze.
2-5. Precautions for Installation in Heavy Snow
Areas
(1) The platform should be higher than the max. snow
depth. (Fig. 2-10)
(2) The 2 anchoring feet of the outdoor unit should
be used for the platform, and the platform should
be installed beneath the air intake side of outdoor
unit.
(3) The platform foundation must be firm and the unit
must be secured with anchor bolts.
(4) In case of installation on a roof subject to strong
wind, countermeasures must be taken to prevent
the unit from being blown over.
2-6. Dimensions of Snow / Wind-proof Ducting
and Refrigerant Tubing Space for Installation
Min. 100
166
DC̲Inverter̲Eng.indd 19
DC̲Inverter̲Eng.indd 19
Min. 100
Duct
308
Outdoor Unit
Unit: mm
Fig. 2-9
In regions with significant snowfall, the outdoor unit should
be provided with a platform and snow-proof duct.
Without snow-
proof ducting
(Low platform)
Fig. 2-10
Outdoor
Unit
Duct
Air
Intake
About 1/2 of the
unit height
Fig. 2-11
19
Air discharge
Without snow-
proof ducting
(High platform)
Duct
Higher than the
maximum
snow depth
Air
Intake
Platform (foundation)
2007/07/25 13:21:37
2007/07/25 13:21:37
GB
FR
DE
IT
PT
GR
ES