Case 4
●
If the power cannot be turned ON separately for the indoor and outdoor units in each system:
(The compressors must be run in order to automatically set the indoor unit addresses. Therefore perform this
step after completing the refrigerant tubing work.)
All-systems automatic address setting: Display item code "AA".
GB
(1) Press the remote controller timer time
longer.)
FR
(2) Next press the
(Automatic address setting is performed in sequence for all outdoor units from No. 1 to No. 30. When automatic
address setting is completed, the units return to normal stopped status.)
<Approximately 15 minutes is required for each system.>
DE
During automatic address setting, "SETTING" blinks on the remote controller display. This display disappears when
address setting is completed.
IT
PT
GR
ES
DC̲Inverter̲Eng.indd 92
DC̲Inverter̲Eng.indd 92
button and
↓
button.
↓
button simultaneously. (Hold for 4 seconds or
Fig. 10-20
92
2007/07/25 13:21:53