Technical Data
Extract, for details refer to the Technical Handbook.
ambient conditions:
IP rating
power consumption
warm-up time (after power-up)
electrical connection
CE marking
dimensions
weight
approvals:
1) The year of construction is indicated by the third letter of the serial number on the type plate: Y = 2007, Z = 2008, A = 2009, B = 2010, C = 2011, etc.
Example: serial number ARYH-0054, the third letter is Y, so the year of construction is 2007.
2) The considered substance must be selected as measuring gas. The calibration must be carried out with the selected substance or alternatively with approx. 50 %LEL propane.
20
o
for operation
–40 to +77
C (–40 to +170
o
during storage
–40 to +85
C (–40 to +180
IP 66 and IP 67, Nema 4X
5.6 W (typical), <7 W (maximum)
1 minute
cable diameter 7 to 12 mm, wire cross-section max. 2.5 mm
Devices and protective systems for use for the intended purpose in explosion-hazard area
(Directive 94/9/EC)
Approx. 160 mm x Ø89 mm
Approx. 2.2 kg (without accessories)
ATEX
Type: IDS 01xx
Dräger Safety • 23560 Lübeck • Germany
0158
II 2G Ex d IIC T6/T4 – DEMKO 07 ATEX 0654417X
II 2D Ex tD A21 IP65 T80
o
C d Ta d +40
–40
Measuring functions for explosion protection (4-20 mA signal output only) acc. to BVS 08 ATEX G 001 X
Type334: benzene, i-butane, n-butane, ethanol, ethylene, n-hexane, methane, methanol, n-nonane, n-octane, n-pentane,
propane, i-propyl alcohol, propylene, toluene - each within a measuring range from 0 to 100 %LEL. Methane
measuring range from 0 to 100 % vol.
Type340: i-butane, n-butane, ethanol, n-hexane, methane, methanol, n-nonane, n-octane, n-pentane, propane, i-propyl
alcohol, propylene, toluene - each within a measuring range from 0 to 100 %LEL, propane measuring range 0 to
500 ppm.
Year of construction (via serial number)
IECEx
Type: IDS 01xx
Dräger Safety • 23560 Lübeck • Germany
Ex d IIC T6/T4 – IECEx UL 07.0009X
Ex tD A21 IP65 T80
o
C d Ta d +40
–40
Year of construction (via serial number)
UL (Classified)
Class I, Div. 1, Groups A, B, C, D / Class II, Div. 1, Groups E, F, G / Class I, Zone 1, Group IIC
T-Code T6/T4, –40
9 to 30 V DC, 9 W - Type 4x
CSA (C-US)
Class I, Div. 1, Groups B, C, D / Class II, Div. 1, Groups E, F, G
T-Code T6/T4, –40
C22.2 No. 152
9 to 30 V DC, 9 W - Type 4x
o
F), 700 to 1300 mbar, 0 to 100% RH
o
F), 700 to 1300 mbar, 0 to 100% RH, non-condensing
o
o
C/T130
C – PTB 07 ATEX 1016
o
o
C/+80
C
1)
o
o
C/T130
C – IECEx PTB 07.0016
o
o
C/+80
C
1)
o
C d Ta d +40
o
o
C/+80
C
o
C d Ta d +40
o
o
C/+80
C
2
2
or 2 x 1 mm
2)