cause electric shock to the operator.
)
2
Do not touch wires and connections to the alternator when the
generator set is running because they are live.
5.2 Stop
1) Turn off every switch and circuit breaker of loads.
2) Keep the engine idle for about 3-5 minutes to allow cool down.
5.3 General precautions during operation
1) Check the value of voltage, current and frequency, which should be desired.
2) Check the value of engine oil pressure and the coolant temperature.
3) Check for any leakage of coolant, oil and fuel.
4) Check for any unusual vibration or noise.
5) Check for any unusual color from the exhaust. Under normal condition, the
exhaust gas has no color or light bluish color.
6) If engine speed is not stable or engine cannot run because of no fuel,
extract the air in the fuel system.
WARNING
1) Press the emergency stop button if an emergency occurs and the
generator must be stopped immediately.
2) Be sure to keep the tolerance among three phases less than 20%. The
load for each phase must below the rated load as well as the current
must less than rated current.
6. Maintenance
Before performing any check or maintenance, stop the engine.
For detailed maintenance procedures on the engine and alternator, refer to
engine and alternator operator's manual.
In hot and dusty environments maintenance procedure of changing engine oil
and oil filter should be performed more frequently.
57