Fuel System; Exhaust System; Dc Electrical System; Periodic Maintenance Schedule - GENERGY GDS20T Instrucciones De Uso

Generador diesel 1500rpm
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

WARNING
1) Do not clean the generator set when the engine is running.
2)
Protect
the
alternator,
air
cleaner,
control
panel
and
electricalconnections form cleaning solvents because cleaning solvents
candamage electrical connections.

6.4.3 Fuel system

Inspect the fuel supply lines, return lines, filters and fittings for leaks during the
machinerunning. Replace worm fuel line components if necessary before leaks
occur.

6.4.4 Exhaust system

Inspect the entire exhaust system including the exhaust manifold, exhaust
elbow, mufflerand exhaust pipe during the machine running.
Visually and audibly check for leaks at all connections, welds, gaskets and
joints.
If any leaks are found out, shut down the machine and do not operate until
corrected.
Replace corroded exhaust components if necessary before leaks occur.

6.4.5 DC electrical system

Inspect the battery terminals for clean and tight connections with the generator
set off.
Loose or corroded connections cause resistance which can impede starting.
Clean andreconnect loose battery cables if necessary.
In order to reduce the possibility of arcing, always disconnect the negative
battery cablefirst and connect it last.

6.5 Periodic maintenance schedule

Following the maintenance schedule and using the machine properly will result
in longergenerator set life, better performance and safe operation. Perform
each maintenanceprocedure at the time period indicated of after the number of
60