Connecting Load Cable; Ground Connections - GENERGY GDS20T Instrucciones De Uso

Generador diesel 1500rpm
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

3.6.2 Connecting load cable

The generator set is ready for user connections. The user load cable should be
connected to the corresponding wire terminal which is located inside the
control cabinet or switch cabinet, then use a wrench to tighten cable
connections and fix them.
Power cables must be placed in suitable channel, tunnels or protective
conduct-holder. Do not include AC and DC cables in the same channeling.
WARNING
Connection must be carried out only by a licensed electrician.

3.7 Ground connections

Metal parts of installation, which are exposed to human or have insulation flaw
or other reasons, may get in contact with voltage. There must be connected to
the ground.
The generator and its electrical components have been equipped with their
correspondent grounding terminals, all connected to a ground strip of the
generator power cabinet. This strip is connected to the grounding terminal that
is in the frame base. Connect the ground terminal of the generator base to the
ground.
The connection from the generator to the grounding must be done with twisted
copper conducting cables with a minimum section of 16mm
unavailability, galvanized iron with a section of 50mm
The ground rod will be installed during construction before the arrival of the
generator. The position, length and diameter of the earthing rod may vary
and will be determined in each case for the corresponding project, if there is
not a project, request a study to an electrical engineering to ensure that the
grounding meets all requirements to ensure safety and regulations.
WARNING
1) If the grounding terminal is unconnected by mistake or accident, it will
be very dangerous for human because leaking current inevitably goes
through the body.
2) All the bonnets of the loads must be grounded to the earth.
3) Grounding should be made before running the generator set.
2
.
50
2
, or in case of
Tabla de contenido
loading