Westinghouse WH3250 Manual Del Propietário página 24

Ocultar thumbs Ver también para WH3250:
Idiomas disponibles

Idiomas disponibles

Avoid prolonged skin contact with
gasoline. Avoid prolonged breathing
of
gasoline
vapors.
STARTING
THE GENERATOR
Before starting the generator,
review
Safety on page 7.
Before attempting to start the generator, verify the
following:
The engine is filled with engine oil (see Checking
Engine Oil on page 29).
The generator is situated in a proper location (see
Location Selection on page 22).
The generator is on a dry surface (see Weatherand
Dry Surface on page 22).
All loads are disconnected from the generator (see
No Connected Loads on page 22).
The generator is properly grounded (see Grounding
the Generator on page 22).
The engine is equipped with a low oil shutdown
switch. If the oil level becomes low, the engine will
shut down and will not start until the oil is filled to the
proper level.
Be sure the engine has the proper oil level before
using. Failure to verify that the engine has the proper
oil level could result in engine damage.
Disconnect all loads from the generator before
starting. Failure to verify all loads are disconnected
prior to starting the generator could result in damage
to the connected appliances.
Manually
Starting
a Generator
NOTE:
This procedure can also be used on an
electric
start generator.
1.
Make sure the circuit breakers are properly set (see
Figure 21).
Never use the generator
in a location
that is wet or damp. Never expose the
generator to rain, snow, water spray or
standing
water while in use. Protect the
generator
from all hazardous
weather
conditions.
Moisture or ice can cause a
short circuit or other malfunction
in the
electrical
circuit.
Never operate the generator
in an
enclosed
area. Engine exhaust
contains
carbon monoxide.
Only
operate the generator
outside
and away
from windows,
doors and vents.
Figure 21 - Breakers
1 - 240/120V Main
Circuit Breaker
Operating
Position
2 - 240/120V Main
Circuit Breaker
Tripped Position
3 - 120V Circuit
Breaker
Operating
Position
4-
120V Circuit
Breaker Tripped
Position
24
WESTPRO
POWER
SYSTEMS
loading