II.2.2
Clearance
IMPORTANT !
The unit should be po sitioned to comply with the
minimum recommend ed clear ances, bear ing in
mind the access to water and electrical
connections.
IMPORTANT
Installation that does not satisf y the recommended
clearance will cause m alfunctioning of the unit with
an incr ease in po wer absorbed and a sensitive
reduction of the cooling cap acit y.
L1
L4
TCHVBZ-TCHVIZ 1201-1231- 1281-1311- 1351-1421-1481-1531-1611
L1
L2
L3
L4
L4
TCHVBZ-TCHVIZ 31301- 31351-31401-31461-31521-31591-31631
L1
L2
L3
L4
II.2.3
Distribution of weights
This section of the manual supplies the indications regarding the
distribution of unit weights.
The knowledge of thes e values is of fundamental importance for the
dimensioni ng of the surfac e on whic h the mac hine must be i nstalled.
L3
mm
600
mm
800
mm
1000
mm
3500
L1
L3
mm
600
mm
800
mm
1300
mm
4200
The space above the unit must be free from obstacles. If the unit is
completel y s urrounded by walls, the distances s pecifi ed are still valid,
provided that at l east two adjac ent walls are not higher than the unit
itself. There must be a mini mum gap of at l east 3.5 m between the top
of the unit and any obstacles above it.
L4
L2
TCHVBZ-TCHVIZ 2411-2431- 2461-2511- 2561-2601-2631-2681-
2711-2781-2841-2901-2961-21031-21111- 21181-21261
L2
The installation of the unit is envisioned on the ground and on terraced
roof tops. Correct positioning of the machi ne incl udes levelling on a
surface c apable of bearing its weight.
59
SECTION II: INST ALL ATION AND MAINTEN ANCE
L1
L3
L1
mm
600
L2
mm
800
L3
mm
1000
L4
mm
3500
L2