I.8.4
Input/output board
o The input/output boar d is ess enti ally made up from:
• section includi ng the microprocess or and the memories that manage
the mac hine control algorithm;
• section dedicated to the interfacing towards the s upervision networ k
and the interfac e panel;
• section dedicated to the inputs/outputs that allow interfacing towards
the devices controlled via a ter minal board with removable c onnectors.
U:1 (MASTER board)
DIGITAL INPUTS (ID)
ID1
Serious alarm (external al arm)
ID2
Evaporator water differential pressure switc h
ID3
remote On/off
ID4
Evaporator pump thermal protection (optional)
ID5
Circuit 1 low press ure s witch
ID6
Oil level (in event of SLO acc essor y)
ID7
Phas e monitor
ID8
Double set poi nt (in the c ase of DSP access ory)
ID9
Condenser water differential pressure switc h (optional)
ID10
Remote Summer/Winter (in event of acc. HPH)
ID23011R
Circuit 1 high press ure s witch
ID23012R
Compress or 1 i ntegral protecti on
DIGITAL OUTPUTS (N)
NO1
Evaporator pump control
N02
Winding A compress or 1 c ontactor
N03
Winding B compress or 1 c ontactor (if PWM)
N04
Evaporator 2 pump c ontrol
N05
Circuit 1 solenoid val ve
N06
25% partialisati on val ves (CR3) or loadi ng valve (in the
event of acc. CCL
N07
50% partialisati on val ves (CR2) or unloading valve (in
the event of CCL acc.)
N08
75% partialisati on val ves (CR1)
N09
Circuit 1 liquid injection val ves (optional)
N10
Anti-freez e resistance
N11
General alar m 1
N12
Condenser pump control
N13
Button val ve (CR4)
ANALOGUE INPUTS (B)
B1
Evaporator i nput water probe ( wor k probe)
B2
Evaporator output water probe (anti-freez e pr obe and/or
wor k probe with CCL acc.)
B3
Condenser i nput water temp. pr obe (HPH access ory)
B4
Condenser output water temp. probe (HPH access ory
and/or wor k pr obe with CCL acc.)
B5
4÷20 mA analogue signal to modify Set-point (in the
event of CS acc essor y)
B6
Circuit 1 flow pr obe (opti onal)
B7
High pressure transducer 1 (in the event of BSP and/or
SPS access ory)
B8
Low press ure tr ansducer 1 (in the event of SPS
accessor y)
ANALOGUE OUTPUTS
Y1
0÷10 Vdc modulati ng output for i nverter
pump/c ondens er side water val ve c ontrol (condensation
control).
U:1 (
board)
SLAVE1
DIGITAL INPUTS (ID)
Serious alarm (external al arm)
ID1
ID5
Circuit 2 low press ure s witch
ID6
Oil level (in event of SLO acc essor y)
ID7
Phas e monitor
ID23011R
Circuit 2 high press ure s witch
ID23012R
Compress or 2 i ntegral protecti on
DIGITAL OUTPUTS (N)
N02
Winding A compress or 2 c ontactor
N03
Winding B compress or 2 c ontactor (if PWM)
N05
Circuit 2 solenoid val ve
N06
25% partialisati on val ves (CR3) or loadi ng valve (in the
event of acc. CCL
N07
50% partialisati on val ves (CR2) or unloading valve (in
the event of CCL acc.)
N08
75% partialisati on val ves (CR1)
N09
Circuit 1 liquid injection val ves (optional)
N10
Anti-freez e resistance
N11
General alar m 2
N12
Condenser pump control
N13
Button val ve (CR4)
ANALOGUE INPUTS (B)
B6
Circuit 2 flow pr obe (opti onal)
B7
High pressure transducer 2 (in the event of BSP and/or
SPS access ory)
B8
Low press ure tr ansducer 2 (in the event of SPS
accessor y)
ANALOGUE OUTPUTS
Y1
0÷10 Vdc modulati ng output for i nverter
pump/c ondens er side water val ve c ontrol (condensation
control).
U:2 (SLAVE2 board)
DIGITAL INPUTS (ID)
Serious alarm (external al arm)
ID1
ID5
Circuit 3 low press ure s witch
ID6
Oil level (in event of SLO acc essor y)
ID7
Phas e monitor
ID23011R
Circuit 3 high press ure s witch
ID23012R
Compress or 3 i ntegral protecti on
DIGITAL OUTPUTS (N)
N02
Winding A compress or 3 c ontactor
N03
Winding B compress or 3 c ontactor (if PWM)
N05
Circuit 3 solenoid val ve
N06
25% partialisati on val ves (CR3) or loadi ng valve (in the
event of acc. CCL
N07
50% partialisati on val ves (CR2) or unloading valve (in
the event of CCL acc.)
N08
75% partialisati on val ves (CR1)
N09
Circuit 3 liquid injection val ves (optional)
N11
General alar m 3
N12
Condenser pump control
N13
Button val ve (CR4)
ANALOGUE INPUTS (B)
B6
Circuit 3 flow pr obe (opti onal)
B7
High pressure transducer 3 (in the event of BSP and/or
SPS access ory)
B8
Low press ure tr ansducer 3 (in the event of SPS
accessor y)
ANALOGUE OUTPUTS
Y1
0÷10 Vdc modulati ng output for i nverter
pump/c ondens er side water val ve c ontrol
(condensation c ontrol).
NOTES
Accessor y
Exp lanation
CCL
Cooling line capacity control
CS
Scrolling set-point via 4÷20 mA analogue signal (not
availabl e simultaneousl y with D SP)
SPS
Cooling circuit high and l ow press ure dis play
BSP
0÷10 Vdc anal ogue signal for condensation control ( via
modulati ng water valve or i nverter pump).
DSP
Double Set-point (not available simultaneousl y with CS)
SLO
Compress or oil level sensor
53