Driver 1
EEV
Valve position
Power request
Driver 1
SuperHeat
00.0°C
Evap.Temp.
00.0°C
Suct.Temp
00.0°C
Driver 1
Evap.Press.
00.0Bar
Evap.Temp.
00.0°C
The followi ng screens are li ke the pr evious, only they refer to the status
of the Driver 2 (circuit 2 el ectronic expansion valve management) and
the s tatus of Driver 3 (circuit 3 electronic expansion val ve
management).
I.8.1.3
Management of time zones
The mas ks referring to the function key are the following:
LAN ADDRESS: 00
Clock not
installed
Clock config.
Time:
00:00
Date:
00/00/00
Day:
***
Insert
Clock
Password
On-off timezones
presence
On-off timezones
ON
OFF
F1-1 00:00
00:00
F1-2 00:00
00:00
On-off timezones
F2 ON00:00 OFF00:00
F3 ->
Always ON
F4 ->
Always OFF
On-off timezones
Mon:F1
Tue:F1
Wed:F1
Thu:F1
Fri:F1
Sat:F1
Sun:F1
Insert
Another clock
Password
0000
I.8.1.4
Set-point setting
The mas ks referring to the function key are the following:
Actual setpoint
07.0°C
Summer
set-point
07.0°C
Winter
set-point
40.0°C
Mask for the display of the state
AUTO
of the electronic expansi on
0000
val ve.
000%
Mask for the display of the state
of the electronic thermostatic
val ve.
Mask for the display of the state
of the electronic thermostatic
val ve.
k_Clock
Indication of Cloc k board not
installed.
Configuration of the cloc k
board.
Entering the pass wor d
0000
N
Enabling the on-off time zones.
Enabling the daily time zones.
Mask for setting the weekly
time z ones.
Mask for entering pass word
again.
s_Setpoint
Mask for dis play of ac tual s et-
point
Mask for setting the summer
and/or winter set-point HPH
acc.).
If the DSP acc essor y is enabled, the following is displayed
Summer double
set-point
Winter double
set-point
If the CS access ory is enabl ed (Scrolling set-point via external 4÷20 mA
anal ogue signal by the i nstaller) the Set-point s et on the control panel is
corrected.
In the programming branch fi nd the mas ks for setting the CS s etting in
logical Offset Set- point mode:
Analogue Input 5
external set-point COOL
4 mA
20 mA
Analogue Input 5
external set-point HEAT
4 mA
20 mA
Summer CS chart in Offset logic
3
2
1
0
-1
-2
-3
4
6
8
Example:
With an exter nal anal ogue signal equivalent to 8 mA, the s et-point is
reduced by 1.5°C.
W inter CS chart in Offset logic
3
2
1
0
-1
-2
-3
4
6
8
Example:
With an exter nal anal ogue signal equivalent to 16 mA, the set- point is
increased by 1.5°C.
T
Operati ve set-points
S
External analogue signal (4÷20 mA)
NOTE
Specify the field in whic h the s et-poi nt c an be modified in the order
phas e so that the offs et parameters c an be s et in the factor y.
49
SECTION I: USER
Summer double set-point
07.0°C
Winter double set-point
35.0°C
Summer set-point field of
variation s etti ng
03.0°C
Minimum offset
-03.0°C
Maxi mum offset
Summer set-point field of
variation s etti ng
03.0°C
Minimum offset
-03.0°C
Maxi mum offset
10
12
14
16
18
20
10
12
14
16
18
20
S (mA)
S (mA)