Technical Characteristics Of The Product - Nice MC824L Instrucciones Y Advertencias Para La Instalación Y El Uso

Ocultar thumbs Ver también para MC824L:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 35
01
Press and hold down the "Set" key for approx. 3 seconds;
02
Release the key when LED "L1" starts flashing;
03
Press keys "" or "" to move from the flashing LED to L8 LED ("input LED") for the "Fault log" parameter;
04
Press and hold the "Set" key through to completion of point 06;
Wait approx. 3 seconds until the LEDs representing the levels corresponding to the manoeuvres with faults illuminate.
05
The LED L1 indicates the result of the most recent manoeuvre while L8 indicates the eighth-to-last manoeuvre. If the
LED is on this means that a fault has occurred; if the LED is off, everything is normal;
Press keys "" and "" to select the required manoeuvre: the corresponding LED performs a number of flashes equal
06
to those normally performed by the flashing light;
07
Release the "Set" key.
TABLE 13 - SMXI / SMXIS / OXI / OXIFM / OXIT / OXITFM in mode I or in mode II
Output no. 1
Output no. 2
Output no. 3
Output no. 4
No.
Command
1
Step by step
2
Partial opening 1
3
Open
4
Close
5
Stop
6
Apartment block Step by Step
7
Step by Step high priority
8
Partial open 2
9
Partial open 3
10
Open and block automation
11
Close and block automation
12
Block automation
13
Release automation
14
Courtesy light timer on
15
Courtesy light on-off
when purchasing a new version.
Important! – Local legislation may impose heavy fines in the event of illegal
disposal of this product.
Disposal of buffer battery (if present)
Important! – Even if discharged, the batteries may contain pollutant substanc-
es and therefore must NEVER be disposed of in normal waste collection points.
Dispose of according to separate waste collection methods as envisaged by
current local standards.

TECHNICAL CHARACTERISTICS OF THE PRODUCT

WARNINGS: • All technical characteristics stated refer to an ambient tempera-
ture of 20°C (±5°C). • Nice S.p.a reserves the right to modify the product at any
time while maintaining the same functionalities and intended use.
• MC824L power supply: 230 Vac (+10% -15%) 50/60 Hz
• MC824L/V1 power supply: 120 Vac (+10% -15%) 50/60 Hz
• Nominal power absorbed from mains: 100 W
• Power absorbed by control unit battery connector with "standby-All"
operation (including a receiver with SM type connector): below 100 mW
"S.S." (Step by Step) command
"Partial opening 1" command
"Open" command
"Close" command
TABLE 14 - OXI / OXIFM / OXIT / OXITFM in extended mode II
"S.S." (Step by Step) command
"Partial opening 1" command
"Open" command
"Close" command
Stops manoeuvre
Apartment block control
Gives command even when automation is blocked or commands are in progress
Partial open (Opening of leaf M2 to 1/2 of normal opening)
Partial open (Opening of two leafs to 1/2 of normal opening)
It causes an opening manoeuvre, after which the automation is blocked; the control unit accepts no further commands with the exception
of "Step by step high priority", "Release" automation and (from Oview only) the commands "Release and close" and "Release and open"
It causes a closure manoeuvre, after which the automation is blocked; the control unit accepts no further commands with the exception
of "Step by step high priority", "Release" automation and (from Oview only) the commands "Release and close" and "Release and open"
It causes the manoeuvre to stop and the automation to block; the control unit accepts no further commands with the exception of "Step
by step high priority", "Release" au to mation and (from Oview only) the commands "Release and close" and "Release and open"
It causes the automation to be released and normal operation to resume
The Courtesy light comes on with timed turning off
The Courtesy light turns on and off in step-by-step mode
TABLE 12 - Fault log
Description
• Flashing light output(*): 1 "LUCYB" type flashing light (12 V, 21 W lamp)
• Electric lock output(*): 1 max. 12 Vac max. 15 VA electric lock
• Gate open light output(*): one 24 V max. 4 W lamp (output voltage may
vary between -30% and +50%, output may also control small relays)
• BLUEBUS output: 1 output with maximum load 15 Bluebus units (maxi-
mum 6 pairs of MOFB or MOFOB photocells + 2 pairs of MOFB or MOFOB
photocells assigned as Opening devices + max. 4 MOMB or MOTB control
devices
• STOP Input: For normally closed, normally open or 8.2 kΩ constant resist-
ance contacts in self-learning mode (a change from the memorised state
prompts the "STOP" command)
• PP Input: for normally open contacts (closure of the contact prompts the
Step by Step command)
• OPEN Input: for normally open contacts (closure of the contact prompts the
OPEN command)
• CLOSE Input: for normally open contacts (closure of the contact prompts
the CLOSE command)
• Radio connector: SM connector for SMXI, OXI and OXIFM family receivers
• Radio AERIAL input: 50 Ω for RG58 or similar type cable
• Programmable functions: 8 ON-OFF type functions and 8 adjustable
functions
• Functions in self-learning mode: • Self-learning of devices connected to
the BlueBus output. • Self-learning of type of device connected to "STOP"
3 s
SET
L1
SET
/
L8
SET
3 s
+
SET
English – 9