USE OF THE BURNER
The burner operates fully automati-
cally; therefore it is non necessary
to carry out any kind at adjustment
during its operation. The "block"
position is a safety position reached
by the burner automatically when
some of the components of the
burners or the plant do not work pro-
perly. It is necessary to check then
whether the cause to the problem is
a dangerous one before unblocking
the burner. The causes to the block
may be temporary, for example
when air in inside the pipes. When it
is unblocked, the burner starts ope-
rating properly. If the burner stops
three or four times at a stretch, it
is necessary either to look for the
cause to the problem and solve it or
ask for the intervention of the after
sales service.
The burner can remain in the "block"
position without any limit in time. In
emergency cases it is advisable and
to close the fuel valve, to disconnect
the burner electrically.
AIR REGULATION SERVOMOTOR SQN 30.111A3500 PREVENTILATION WITH AIR OPEN
(2
FLAME POSITION) AIR CLOSED WITH BURNER IN STOP POSITION
nd
A 2
stage valve connection cam (must be adjusted in a
nd
position between the 1
st
B Air regulation cam 1
stage
st
C Close air shutter cam with burner in stop position
D Air regulation cam 2
stage
nd
Motor-cam shaft coupling cutting out pin.
The switching-off of the motor-cam and shaft connection can be obtained by
pushing.
In order to modify the cams regulation it's necessary to intervene on the relative
red rings. Pushing by sufficient strength,in the sens one desires, each red ring
can turn in respect to the reffering scale. The pointer of the red ring indicates
on the respective reffering scale the rotation angle set for each cam.
ELECTRIC DIAGRAM FOR SERVOMOTOR SQN 30
Drawn in the position in which is used
flame and the 2
stage cam)
nd
0006081054_200810