• Installation space. The following figure shows the minimum installation
clearances for the terminal separator kit Ø 80/80 in a limit condition.
ES
PT
GR
PL
TR
CZ
CS
SI
Exhaust (metres)
HU
1
2
RU
3
4
RO
5
* The intake pipe can be increased by 2.5 m if the bend on exhaust is eliminated.
2 m if the intake bend is eliminated or 4.5 m if both bends are eliminated.
IE
270
(including intake terminal with grill and two 90° bends)
NON-INSULATED PIPE
Intake (metres)
36.0*
34.5*
33.0*
32.0*
30.5*
• Extensions for separator kit Ø 80/80. The maximum straight length
(without bends) in a vertical route, for intake and exhaust pipes Ø 80
is 41 m, 40 of which on intake and 1 on exhaust. This total length cor-
responds to a resistance factor of 100. The total usable length, obtained
by adding the length of the intake and exhaust pipes Ø 80, must not
exceed the maximum values given in the following table. If mixed acces-
C42
sories or components are used (e.g. changing from a separator Ø 80/80 to
a concentric pipe), the maximum extension can be calculated by using
a resistance factor for each component or the equivalent length. The sum
of these resistance factors must not exceed 100.
• Temperature loss in fume ducts. To avoid problems of fume condensate
in the exhaust pipe Ø 80, due to fume cooling through the wall, the
length of the pipe must be limited to just 5 m. If longer distances have
to be covered, use Ø 80 insulated pipes with insulation (see insulated
separator kit Ø 80/80).
Max. usable lengths
Exhaust (metres)
6
7
8
9
10
11
12
INSULATED PIPE
Intake (metres)
29.5*
28.0*
26.5*
25.5*
24.0*
22.5*
21.5*