• Extensions for horizontal kit. The horizontal intake/exhaust kit Ø 80/125
can be extended up to a maximum horizontal length of 7300 mm includ-
ES
ing the terminal with grille and excluding the concentric bend leaving
the boiler and the adapter Ø 60/100 in Ø 80/125 (see figure). This
configuration corresponds to a resistance factor of 100. In this case the
PT
special extensions must be requested.
C12
GR
PL
TR
N.B.: When installing the ducts, a section clamp with pin must be
installed every 3 metres.
• External grille.
N.B.: For safety purposes, do not even temporarily
obstruct the boiler intake/exhaust terminal.
CZ
Vertical kit with aluminium tile Ø 80/125. Kit assembly: install the con-
centric flange (2) on the central hole of the boiler, inserting the seal (1) and
tighten using the screws supplied with the kit. Fit the male end (smooth)
CS
of the adapter (3) in the female end of the concentric flange (2). Installing
the imitation aluminium tile. Replace the tiles with the aluminium sheet
(5), shaping it to ensure that rainwater runs off. Position the fixed half-shell
(7) on the aluminium tile and insert the intake/exhaust pipe (6). Fit the
SI
male end (smooth) of the Ø 80/125 concentric terminal pipe (6) up to
the stop on the female end of the adapter (3) (with lip seals), making sure
that the relevant ring (4) is fitted; this will ensure hold and joining of the
elements making up the kit.
HU
RU
RO
5
IE
4
3
2
1
• Coupling extension pipes and concentric elbows. To install possible cou-
pling extensions on other fume extraction elements, proceed as follows:
fit the male end (smooth) of the concentric pipe or concentric elbow up
to the stop on the female end (with lip seals) of the previously installed
element; this will ensure correct hold and joining of the elements.
Important: if the exhaust terminal and/or extension concentric pipe needs
shortening, consider that the internal duct must always protrude by 5 mm
with respect to the external duct.
This specific terminal enables fume exhaust and combustion air intake in
a vertical direction.
N.B.: The vertical kit Ø 80/125 with aluminium tile enables installation on
terraces and roofs with maximum slope of 45% (24°) and the height between
the terminal cap and half-shell (374 mm) must always be respected.
268
8
The kit comprises:
7
1 - Seal (1)
1 - Female concentric
flange (2)
1 - Adapter Ø 60/100
for Ø 80/125 (3)
1 - Ring(4)
1 - Aluminium tile (5)
1 - Intake/exhaust concentric
6
pipe Ø 80/125 (6)
1 - Fixed half-shell (7)
1 - Mobile half-shell (8)
This vertical kit configuration can be extended to a maximum length of
12200 mm in a vertical straight route, including the terminal (see figure
below). This configuration corresponds to a resistance factor of 100. In this
case the specific coupling extensions must be requested.
The terminal Ø 60/100 can also be used for vertical exhaust, in conjunc-
tion with concentric flange code no. 3.011141 (sold separately). The height
between the terminal cap and half-shell (374 mm) must always be respected
(see drawing below).
The vertical kit with this configuration can be extended to a max. straight
vertical length of 4700 mm, including the terminal (see the figure below).
C32
C32