Pages 3 and 4 – Digital Inputs
Digital Inputs:
Each digital input will have an indication showing whether the input is in
an "OPEN" or "CLOSED" state. This is the physical state of the input and may
not necessarily line up with the logical condition. The normal state is shown
below.
Emergency Stop – Normally Closed
Main/Fan Motor Overload – Normally Closed
Remote Load Enable – Normally Open
Remote Load/Unload – Normally Open
Remote Start - Normally Open
Remote Stop – Normally Closed
Dryer Temperature Fault – Normally Open
Dryer High Pressure – Normally Closed
Pages 5 & 6 – Digital Outputs
Digital Outputs:
Each digital output will have an indication showing whether the output is in
an "OPEN" or "CLOSED" state. This is the physical state of the input and may
not necessarily line up with the logical condition. The normal state is shown
below.
Starter Contact KM1, KM2 – Normally Open
Starter Contact KM3 – Normally Open
Fan Starter Contact KM4 – Normally Open
80447162 Rev B
Figure 90 : Digital inputs
Figure 91 : Digital inputs
Load Solenoid 1SV – Normally Open
Modulation Solenoid 3SV – Normally Open
Dryer Run / Fan Run – Normally Open
PORO Horn – Normally Open
Trip Indication – Normally Open
Page 7 – Analog Outputs
Figure 92 : Analog inputs
Analog Outputs:
The value for the analog outputs will be in mA.
VSD Blower Output – Current speed of the VSD blower (if installed).
Page 8 – CT Inputs
Figure 93 : CT Inputs
CT Inputs
Displays the mA value of the current transformers installed on each leg of the
motor incoming power
CT1
CT2
CT3

Factory Settings folder

This folder is for Ingersoll Rand factory and service personnel. A password
must be entered on page one in order to adjust values in this folder. This
folder is used for setting parameters that are specifi c to that compressor and
displaying software information for the controller.
Page 1 – Password
Figure 84 : Password
Password:
Provides access to enter a valid password to gain access to password
protected parameters. The password is entered by scrolling down to the
password value and pressing the return key.