93014.15.06
EN
•
Run Hours indicate the number of hours the compressor has been
running.
The online and offl ine set points can be selected and modifi ed on this
page. All other information on this page is read only.
Page 2 : Counters
•
Hour Meters indicate the hours that: the controller has been powered
up, the compressor has been running, and the compressor has running
loaded.
•
Starts indicate the number of times a start is attempted on the
compressor.
•
Date & Time is adjustable and confi gurable in the General Settings folder.
Pages 3-4: Analog Inputs
All information on these pages is read only.
The following inputs are displayed in this section:
•
Package Discharge Pressure
•
Sump Pressure
•
Airend Discharge Temperature
•
Injected Coolant Temperature
•
After-cooler Discharge Temperature
•
Separator Pressure Drop
EN-14
NOTICE
Figure 12 : Counters
Figure 13 : Analog Inputs
Icon
Meaning
Pressure
Temperature
NOTICE
•
Coolant Filter Pressure Drop
•
Inlet Vacuum
•
After-cooler Discharge Pressure (integrated dryer compressors only)
•
Remote Pressure (optional)
Operator settings folder
Pages 1-2: Operator Settings
Figure 14 : Operator Settings
Table 10 : Operator Settings
Operator
Selection
Min.
Settings
Offl ine
---
75
Pressure
Online
---
65
Pressure
Lead/Lag
Lead/Lag
---
Lag Off set
---
0
Mode of
Mode
---
Operation
Condensate
---
2
Release
Condensate
---
90
Interval
Stop Delay
---
10
Time
Star-Delta
---
5
Time / Start
Time
Pages 3-5: Operator Options
Figure 15 : Operator Options
Max.
Default
Step
Rated+10
Rated+10
1
Offl ine-10
Offl ine-10
1
---
Lead
---
45
0
1
---
ON/OFF
---
line
20
5
1
270
180
1
30
10
1
30
10
1
80447162 Rev B
Unit
psi
psi
---
psi
---
sec
sec
sec
sec