APPLICATION OF THE BURNER TO BOILER for
model COMIST 72 - 122 - 250 - 300 DSPGM (steel
fixing flange)
1 Boiler plate
2 Flange with insulating materials
3 Seam with insulating materials
4 Burner securing flange
5 Stud bolts, washers and nuts for fastening to the boiler
6 Nuts screws and washers to fasten flange to the sleeve
COMBUSTION HEAD ASSEMBLY
Following the drawing, connect the tube on the attachment on
the flange and fix with the screw
To put in place insulation flange 2, which must be positioned
between the burner and the plate of boiler 1, the end of the
combustion head must first be removed.
a) Adjust position of connector flange 4 by loosening screws 6
so that the combustion head penetrates into the combustion
chamber the amount recommended by the generator's ma-
nufacturer.
b) Position seal insulation 3 on the tube unit.
c) Fasten the combustion head assembly to the boiler 1 using
the stud bolts, washers and the nuts provided 5.
d) With suitable material, completely seal the space
between the tube unit of the burner and the hole
on the refractory plate inside the boiler door.
APPLICATION OF THE BURNER TO BOILER
for model COMIST 180 DSPGM
1 - Boiler plate
2 - Insulating gasket
3 - Burner fixing flange
4 - Elastic collar
5 - Stud bolt
6 - Locking nut with washer
7 - Nut and washer for fastening the first flange
7 / 30
0006080115_200909
E
N
G
L
I
S
H