Faults search

Other than the following list of possible problems, the warnings are provided on the display, as indicated in chapter 9.5.
Problem
The automation does not open or close.
The automation does not execute the
functions set.
Movement of the doors is not linear or
movement is inverted for no reason.
The automation opens but does not
close.
The safety devices do not intervene.
The automation opens by itself.
The locking device does not lock or does
not unlock the doors.
Possible cause
No mains power supply (display off).
Burnt mains fuse (display off)
Accessories outside the short circuit.
The door is locked with latches or locks.
Functions selector with wrong setting.
Command or safety devices are always enabled.
Automation did not correctly detect the stop
measurements.
The safety devices test causes anomalies.
The opening devices are enabled.
Automatic closure is not working.
Wrong connections between the safety devices and
electronic control.
The opening and safety devices are unstable or detect
bodies in motion.
EMERGENCY automation is executing the emergency
opening test.
EMERGENCY automation has detected an anomaly
Wrong connection of the locking device on electronic
control.
The lock coupling brackets, fastened on the carriages, do
not release from the locking device.
Pulling the unlocking cord, the doors do not unlock.
Intervention
Check the mains power supply is present.
Replace the mains fuse
Disconnect all the accessories from the terminals
-24V/+24V and reconnect them one at a time (check
the presence of 24V voltage).
Check the doors move freely.
Check and correct the functions selector settings.
Disconnect the devices from the terminal boards and
check the door is working.
Reset by switching the automation off and back on.
Bridge one contact at a time TS/OS-R TS/OS-L
TS/OS-R TS/OS-L.
Check the opening sensors are not subject to
vibrations, do not make false detections or the
presence of objects in motion in the action range.
Check the settings of the functions selector.
Check the safety contacts of the devices are correctly
connected to the terminal boards and the relevant
jumpers were removed.
Check the opening sensors are not subject to
vibrations, do not make false detections or the
presence of bodies in motion in the action range.
Wait for the test to execute.
Check the electrical mains is present.
Check the battery connection and its efficiency.
Check the 1-EO contact closure.
Check the functions selector is in protected mode (the
lock symbol must be lit).
If present, check the position of the locking device and
connection 1-S1.
Check correct connection of the cable colours on the
locking device.
Check adjustment of the position of the lock coupling
brackets.
Check correct fastening of the unlocking cord on the
locking device.
25