Advanced Parameters Menu - myone LUCE R Manual De Instalación Y Mantenimiento

Puertas correderas
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

RAMP
Acceleration time setting. Choose between the minimum and maximum value:
ACCELERATION
minimum value = 100 ms (maximum acceleration)
TIME
maximum value = 2000 ms (minimum acceleration)
BTMD
Setting the battery power supply device operation, in a power failure. Choose from the following values:
BATTERY
NO = battery not connected
MODE
EMER = emergency opening (EMERGENCY - Automatic selection for Emergency automations)
CONT = continuation of normal door operation, with last opening manoeuvre
N.B. the number of manoeuvres and the duration with the battery depends on the efficiency of the battery, the
weight of the leaves and the friction present.
UNLK = The unlocking device uncouples and the door does not move.

11.2 ADVANCED PARAMETERS MENU

Using the buttons ↑ and ↓ choose the ADV menu, press ENTER to select and adjust the advanced parameters.
Display
Description
OSSM
Slowing space setting of the safety sensors in opening (see terminals 6A/6B). Choose from the following values:
OPENING
NO = no slowing
SAFETY
100 / 200 / 300 / 400 / 500 = the door slows in the last 100/ 200/ 300/ 400/ 500 mm of opening
MOTION
YES = the door slows during the entire opening
OSSS
Stoppage space setting of the safety sensors in opening (see terminals 6A/6B). Choose from the following
OPENING
values:
SAFETY
NO = no stop
STOP
100 / 200 / 300 / 400 / 500 = the door stops in the last 100/ 200/ 300/ 400/ 500 mm of opening
TYLK
Locking device type selection. Choose from the following values:
LOCK TYPE
LK1 = bistable locking device (SL5LD)
LK2 = magnetic brake device (SL5SB)
ELLK
Locking operation type selection. Choose from the following values:
LOCK
AUTO = unlocked with automatic operation and locked with one-directional operation and door closed
OPERATION
UNLK = always unlocked with automatic and one-directional operation (EMERGENCY - Automatic selection for
TYPE
Emergency automations)
LOCK = always locked and door closed
PUCL
Thrust on stop closed setting. Choose from the following values:
PUSH DOOR
No = no thrust
CLOSED
MIN = slight thrust
MED = medium thrust
MAX = strong thrust
PIPP
Thrust on stop open setting. Choose from the following values:
PUSH DOOR
No = no thrust
OPEN
YES = thrust enabled
HOLD
Hold door open thrust setting. Choose from the following values:
HOLD DOOR
No = no thrust
OPEN
MIN = slight thrust
MED = medium thrust
MAX = strong thrust
PUGO
Enabling of door on thrust. Choose from the following values:
PUSH & GO
No = disabled
YES = enabled
TAKO
Open door time setting, after 1-KO command. Choose between the minimum and maximum value:
KO-CLOSING
NO = see MENU > TAC setting
TIME
minimum value = 1 s
maximum value = 30 s
VTAC
Variable automatic closing time based on pedestrian traffic. Choose from the following values:
VARIABLE
No = disabled
CLOSING
YES = enabled
TIME
MOT
Manual sliding of the door setting (only with power present), using the electrical connection of the motor windin-
MOTOR
gs. Choose from the following values:
CIRCUIT
OC = manual opening of the door without friction (motor with windings open)
SC = manual opening of the door with friction (motor with windings in short circuit)
18
600
NO
Default settings
500
NO
LK1
AUTO
MIN
NO
NO
NO
NO
YES
OC