T41
Test enabling for safety devices (in compliance with standard EN16005) Choose from the following values:
SAFETY TEST
NO = test disabled
YES = test enabled
SL5E
In the event of an emergency, you can disable operation as an emergency exit. Choose from the following values:
EMERGENCY
NO = emergency exit disabled
DOOR
YES = emergency exit enabled
PULY
Motor pulley type setting. Choose from the following values.
MOTOR
15 = WHITE motor pulley with 15 serrations
PULLEY
18 = BLACK motor pulley with 18 serrations
SYNC
Two automations per leaf with synchronised movement. Choose from the following values.
DOOR
NO = no synchronisation
SYNCHRONI-
MST1 = MASTER automation
ZATION
SLV1 = SLAVE automation
MST2 = MASTER external automation (see menu: ADV > INK > EXT)
SLV2 = SLAVE external automation (see menu: ADV > INK > EXT)
INK
Interlocked operation between two doors, i.e. opening of a door is only permitted when the other door is closed.
INTER-
Choose from the following values.
LOCKED
NO = no interlock
DOOR
INT = internal door
EXT = external door
EMID
When two EMERGENCY automations are connected using the terminals 1-H-L, they must have different identi-
EMERGENCY
fication numbers. Choose from the following values: 0 / 1 / 2 / 3.
IDENTIFIED
STG1
Input commands between terminals 1-G1. Choose from the following values.
G1-SETTING
NO = No function
STOP = Stop command (N.C.). Opening of the contact 1-G1 causes stoppage of the door (EMERGENCY
Selection not available for Emergency automations).
STEP = Step-step command Closure of the contact 1 - G1 causes in sequence opening (automatic closure
disabled) and closure of the door.
SAM = Automatic selection command of the function selector. Closure and opening of the contact 1-G1 changes
the functions selector mode (see menu settings: SEL > SAM1 and SEL > SAM2).
EMER = Emergency opening command (N.C.). Opening of the contact causes the door to open.
PART = Partial opening command (see menu settings: MENU > PART > 10-90).
CAB = Step-step command. Closure of the contact 1 - G1 causes in sequence closure of the door (commands
3A/3B disabled, room occupied signalling enabled) and opening of the door (re-enabling commands 3A/3B,
occupied room signalling disabled).
INKE = Interlocked operation bypass command between two doors (see menu: ADV > INK).
YES
YES
15
NO
NO
0
NO
19