FUEL FEEDING HYDRAULIC DIAGRAM FOR ONE OR MORE LIGHT OIL BURNERS WITH MAXIMUM NOMINAL
VISCOSITY (5 °E at 50 °C) FROM 75 TO 300 DSPG
1
Main cictern
2
Filter
3
Circulation pump
4
Water and system drain
6
Fuel recovery and degasifier
7
One-way valve
8
By-pass (usually closed)
9
Feeding circuit presure regulator
adjustment range between 0.2 and 1 bar
10 Pressure gauge (0 - 4 bar)
DIAGRAM OF PIPES OF FEED SYSTEM FOR LIGHT OIL BURNERS WITH MAXIMUM NOMINAL VISCOSITY
(5 °E at 50 °C)
1
Main cictern
2
Filter
3
Circulation pumps
4
Water and system drain
5
Air-gas drain usually closed
6
Fuel recovery and degasifier
7
One-way valve
8
By-pass (usually closed)
The combustible recovery and degasifier tanks (diameter ~ 150, height
~ 400) should be installed as near as possible to the burner and should
be about 0,5 m. higher with respect to the burner's pump.
The combustible recovery and degasifier tanks (diameter ~ 150,
height ~ 400) should be installed as near as possible to the burner
and should be about 0,5 m. higher with respect to the burner's pump.