• Generous: the control is active until the deviation is less than 50 mbar. The
control is reactivated if the deviation exceeds 100 mbar.
Factory setting: Plug&Play
8.6.8 Pressure range
The parameters of the "p-Range" menu can only be set for "Smart"
type devices.
With AV-EP pressure regulators for fieldbus connection, the parameter
settings from the "p-Range" menu are overwritten by the fieldbus.
Minimum set point w
min
The device actively works (controls the pressure) within the range w
where w
> p
. w
is therefore to be considered as an entry point.
min
min
min
The following settings are possible:
Value range:
6-bar devices: 0.5 ... 6 bar (1 – 87 psi)
10-bar devices: 0.5 ... 10 bar (1 – 145 psi)
Increments: 0.1 bar (1 psi)
Factory setting: 0.1 bar
The value range 0.1 ... 0.4 bar is not guaranteed.
Recommended initial value: ≥ 0.5 bar.
Beginning of pressure range p
The beginning of the pressure range p
characteristic curve and therefore the zero point of the device characteristic
curve. In most cases the following applies: p
The following settings are possible:
Value range:
6-bar devices: 0 ... 3 bar (0 – 44 psi)
10-bar devices: 0 ... 5 bar (0 – 73 psi)
Increments: 0.1 bar (1 psi)
Factory setting: 0 bar
End of pressure range p
max
The end of the pressure range p
acteristic curve.
The following settings are possible:
Value range:
6-bar devices: 1.2 ... 6 bar (17 – 87 psi)
10-bar devices: 2 ... 10 bar (29 – 145 psi)
Increments: 0.1 bar (1 psi)
Factory setting:
6-bar devices: 6 bar
10-bar devices: 10 bar
AVENTICS™ AV-EP | R414007537-BAL-001-AB | English
min
defines the lowest pressure value of the
min
= 0 bar.
min
defines the highest pressure value of the char-
max
– p
,
min
max
Dynamics
Entry
Accuracy
Entry
Serial nr
Display
Fig. 10: Navigation
8.6.9 Display
Language
Defines the language in which the control/navigation is shown on the display.
The following settings are possible:
Value range: German, English, French
Factory setting: English
Unit
Defines the unit system in which the pressure-related values are displayed. Pres-
sure-related values include the actual pressure value, the manually or externally
specified pressure set point, the hysteresis threshold values, and the pressure
range adjustments. The following settings are possible:
Value range: bar, psi
Factory setting: bar
Contrast
Defines the contrast settings for the display. The following settings are possible:
Value range: 15 % – 32 %
Increments: 1 %
Factory setting: 25 %
Dynamics
Defines the response sensitivity for displaying the set point and actual value. The
following settings are possible:
Value range: high, middle, low
Factory setting: middle
Backlight
Defines the time when the display backlight automatically switches off if no but-
ton is pressed. The following settings are possible:
Value range: 1 min, 3 min, 5 min, On
Factory setting: 3 min
Standard screen
Information
Control
("Smart" type devices)
p-Range
("Smart" type devices)
Display
Analog I/O
(M12 devices)
Switched Out
(M12 devices)
Entry
w min
Entry
p min
p max
Entry
Entry
AV-EP NR
Display
Ctrl type
Units
Display
Entry
Software
Display
Password
Entry
LEVEL 1
Memory
Entry
Lock
Entry
Force
(no timeout)
Entry
LEVEL 2
Hysteresis
Entry
Delay
Entry
Language
Entry
Backlight
Entry
Contrast
Dynamics
Entry
Entry
29