Appendix A
13. Shut OFF utility power and make sure the generator starts
automatically after the line interrupt delay.
14. Switch the utility breaker to ON and make sure that power is
automatically transferred back to the utility.
15. Shut OFF utility power again to automatically start the
generator. When power has transferred to the generator, close
each of the breakers in the distribution panel one at a time
until the generator has accepted the entire load.
14
16. With the generator carrying the entire load, recheck gas
pressure to verify that it's at the same level it was before the
generator was started.
Even if the generator is running smoothly at
this point, a drop in gas pressure indicates that
the supply is barely adequate to supply the
generator's needs. Changes in the generator load,
or additional gas demand by other appliances
may affect the generator's performance. Verify
gas pressure and pipe sizing. Unhook the
manometer and reinstall the port plug.
17. Switch the utility breaker ON to restore utility power to the
home.
18. The generator will continue to run to allow the engine to cool
down, then shut itself off.
19. Shut OFF utility power again. The generator should start and
the entire priority load should transfer to the generator.
NOTE: