Battery Installation - Honeywell G0060341 Guia De Instalacion

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

8. Connect the white neutral wire to the neutral bus bar and
torque to 35 inch lbs. The torque values are:
• 10-14 AWG = 35 in/lbs
• 8 AWG = 40 in/lbs
• 4-6 AWG = 45 in/lbs
9. Connect the control wires to the correct terminals. The
terminals are clearly marked N1 and N2 for utility sensing; 23
and 194 for transfer relay control; and T1 and 0 for battery
charge. On pre-wired switches, the 0 (zero) wire will not be
present/required.
In order to maintain separation of circuits, the
DC control wires must be separated from the AC
control wires. A piece of fiberglass sleeving has
been provided in the manual kit to achieve this.
Slide the sleeving over the AC wires OR the DC
wires, but not both, from the wire landing area
to the outside of the generator. Use the cable tie
locations to hold the sleeving in place.
10. An improperly connected control wire can damage the
generator control board.
11. For 10-20 kW models, locate the metal hasp that is packaged
in the owner's manual bag. Insert the hasp in the slot located
on the left side of the external circuit breaker box. Be sure that
the clip of the hasp is facing toward the front of the generator.
If desired, lock the external box.
Neutral
Ground
Cable Tie Location
NOTE:

BATTERY INSTALLATION

1. Before purchasing a battery for the generator, refer to the
Owner's Manual for the recommended battery.
• Group 26R, 12 Volt, 525cca minimum
2. Follow all of the procedures and safety precautions in the
generator Owner's Manual when installing the battery.
Verify the switch is in the off position. When preparing for
operational testing, DO NOT connect the battery until transfer
switch connections are complete.
General Information
9
Tabla de contenido
loading

Tabla de contenido