Led Diagnosis On The Bus Coupler; Reading The Diagnostic Display On The Bus Coupler; Conversion Of The Valve System - Emerson AVENTICS EtherCAT Descripción De Sistema

Acoplador de bus aes/controladores de válvula av
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 84
Risk of uncontrolled movements when switching on the system!
There is a danger of personal injury if the system is in an undefined state.
1. Put the system in a safe state before switching it on.
2. Make sure that no personnel are within the hazardous zone when the com-
pressed air supply is switched on.
1. Switch on the operating voltage.
The controller sends parameters and configuration data to the bus coupler,
electronic components in the valve zone, and I/O modules during startup.
2. After the initialization phase, check the LED statuses on all modules (see "LED
Diagnosis on the Bus Coupler") and system description of the I/O modules.
Before applying the working pressure, the diagnostic LEDs may only be illumi-
nated in green, as described in Table 12:
Table 12: Status of the LEDs on commissioning
Designation
Color State
UL (14)
Green Illuminated
UA (15)
Green Illuminated
IO/DIAG (16)
Green Illuminated
RUN (17)
Green Illuminated
L/A 1 (18)
Green Flashes
1)
quickly
L/A 2 (19)
Green Flashes
1)
quickly
1)
At least one of the two LEDs L/A 1 and L/A 2 must be illuminated or flashing in
green.
If the diagnostic run is successful, you may commission the valve system. Other-
wise, the errors must be remedied (see "Troubleshooting").
Switch on the compressed air supply.
u

11 LED Diagnosis on the Bus Coupler

The bus coupler monitors the power supplies for the electronic components and
actuator control. If they exceed or fall below a set threshold, an error signal will
be generated and reported to the controller. In addition, the status is displayed
by the diagnostic LEDs.

Reading the diagnostic display on the bus coupler

The LEDs on the top of the bus coupler report the messages listed in Table 13.
Before commissioning and during operation, regularly check the bus coupler
u
functions by reading the LEDs.
AVENTICS™ EtherCAT | R412018142-BAL-001-AG | English
CAUTION
14
UL
15
UA
16
IO/DIAG
RUN
17
L/A 1
L/A 2
18
19
Meaning
The electronics supply voltage is greater than the
lower tolerance limit (18 V DC).
Actuator voltage exceeds the lower tolerance
limit (21.6 V DC).
The configuration is OK and the backplane is
working perfectly.
The bus coupler exchanges cyclical data with the
controller.
Connection with Ethernet device on fieldbus con-
nection IN
Connection with Ethernet device on fieldbus con-
nection OUT
Table 13: Meaning of the diagnostic LEDs
Designation
Color
State
UL (14)
Green
Illumi-
nated
Red
Flashes
Red
Illumi-
nated
Green/red
Off
UA (15)
Green
Illumi-
nated
Red
Flashes
Red
Illumi-
nated
IO/DIAG (16)
Red
Illumi-
nated
Red
Flashes
RUN (17)
Green
Illumi-
nated
Green
Isolated
flashes
Green
Flashes
Green
Off
L/A 1 (18)
Green
Illumi-
nated
Green
Flashes
quickly
Green
Off
L/A 2 (19)
Green
Illumi-
nated
Green
Flashes
quickly
Green
Off

12 Conversion of the Valve System

Danger of explosion caused by defective valve system in an explosive atmos-
phere!
Malfunctions may occur after the configuration or conversion of the valve sys-
tem.
After configuring or converting a system, always perform a function test in
u
a non-explosive atmosphere before recommissioning.
This chapter describes the structure of the complete valve system, the rules for
converting the valve system, the documentation of the conversion, as well as the
re-configuration of the valve system.
14
UL
15
UA
16
IO/DIAG
RUN
17
L/A 1
L/A 2
18
19
Meaning
The electronics supply voltage is greater than the
lower tolerance limit (18 V DC).
The electronics supply voltage is less than the
lower tolerance limit (18 V DC) and greater than
10 V DC.
The electronics supply voltage is less than
10 V DC.
The electronics supply voltage is significantly less
than 10 V DC (limit not defined).
Actuator voltage exceeds the lower tolerance
limit (21.6 V DC).
The actuator voltage is less than the lower toler-
ance limit (21.6 V DC) and greater than UA-OFF.
The actuator voltage is less than UA-OFF.
Diagnostic message from module present
Valve unit incorrectly configured or backplane
function error
Bus coupler status is OPERATIONAL
Bus coupler status is SAFE-OPERATIONAL
Bus coupler status is PRE-OPERATIONAL
Device is in INIT status
The physical connection between the bus coupler
and network has been detected (link established).
Data packets received (flashes for each data
packet received)
The bus coupler does not have a physical connec-
tion with the network.
The physical connection between the bus coupler
and network has been detected (link established).
Data packets received (flashes for each data
packet received)
The bus coupler does not have a physical connec-
tion with the network.
DANGER
33