|
en
Instrument settings
11.4 Configuring function key
1. Select Settings > Instrument > Function key and
confirm.
2. Select a function and confirm.
Graph
The measurements of the past 15 minutes
are displayed as a time/concentration
graph.
Faults
Fault messages are displayed in plain text.
Warnings
Warning messages are displayed in plain
text.
Bump test
The bump-test allows applying gas to the
sensor without generating an alarm. The
maintenance signal is transmitted. After 15
minutes or tapping [OK] again ends the
bump test and the instrument returns to nor-
mal operation.
Sensor vital-
Shows the remaining sensor vitality.
1)
ity
1) Only with diagnostic dongle
11.5 Resetting to default settings
This function resets the instrument to factory default settings.
1. Select Settings > Instrument > Device init and confirm.
2. Select Confirm and confirm with [OK].
11.6 Combinations of latching and alarm
acknowledgment
The following examples give an overview of relay
acknowledgment combinations.
Latching
(Manual relay reset)
Acknowledge-
Relay reset possible at any time.
able
Non-acknowl-
Relay reset not possible before alarm con-
edgeable
dition cleared.
Pre-acknowl-
Alarm acknowledgment possible before the
edgeable
alarm condition cleared. The relay resets
automatically after the alarm condition
cleared.
Latching and non-latching signals are not time-limited.
Latching signals stay active until they are acknowledged.
Non-latching signals stop as soon as the triggering condition
clears.
11.7 Relays
With factory default settings and during normal operation, the
relays are energized. This provides a "fail-safe" operation.
22
For PointGard instruments the setting Normally energ. must
not be changed to Energ. on alarm, otherwise the built-in
alarm devices (horn and strobes) are triggered!
11.7.1 Configuring relay A1 or A2
This function defines whether the alarm relay is energized
during normal operation or energized at an alarm condition.
1. Select Settings > Instrument > Alarm> Relay A1 or
2. Select the desired option and confirm.
11.7.2 Setting fault relay warm-up 1
This function is used to set operation of the fault relay during
warm-up 1 to indicate the warm-up 1 state on the relay output.
1. Select Settings > Instrument > Alarm> Fault warm up
Non-Latching
(Automatic relay
reset after alarm
condition cleared)
11.8 Alarm configuration
All alarm settings have influence on the relays, the analog
interface, and the built-in alarm devices.
11.8.1 Switching the alarms on or off
1. Select Settings > Instrument > Alarm > Alarm on/off.
Relay A2 and confirm.
Normally
The relay contact is energized during nor-
energized
mal operation and changes if an alarm is
triggered. At a loss of power this triggers an
alarm (fail-safe).
Energ. on
If an alarm is triggered, the relay contact is
alarm
energized.
the desired option and confirm.
static
The fault relay triggers a connected alarm
indicator permanently.
The orange LED is lit continuously.
dynamic
The fault relay switches state for 9 seconds.
Example:
– A horn is connected to fault relay output
Normally Open.
– Relays are configured as normally ener-
gized.
The horn and the orange LED of the
transmitter are 1 second active and 9
seconds in-active.
Enable
Disable
Instructions for use
Alarm signaling is on.
Alarm signaling is off.
LEDs, relays and interfaces
do not indicate an alarm con-
dition.
The 4-20mA interface trans-
mits the maintenance signal.
The measured value and the
symbol
are displayed.
The fault relay indicates a
fault.
|
Dräger PointGard 2000 Series