Notes on the programmer
Programmer sequence
Times Legend
time (50 Hz) in seconds
Pre-ventilation time with air damper open
1.5............t1
Safety time
.................t2
Safety time or safety time with burners that use pilot burners
- .................t2'
6.................t
Short pre-ignition time (ignition transformer on terminal 16)
- .................t'
Long pre-ignition time (ignition transformer on terminal 15)
Time between beginning of t2' and valve consensus on terminal 19 with t2
1...............t4
Time between beginning of t2' and valve consensus on terminal 19
- .................t4'
Time between end of t4 and consensus at power regulator or at valve on terminal 20
1...............t5
Post-ventilation time (with M2)
18...............t6
Time between consensus for start-up and voltage at terminal 7 (start delay for fan motor M2)
.................t7
Start-up duration (without t11 and t12)
7...............t8
Second safety time for burners that use pilot burners
.................t9
1...............t10 Time from start-up to beginning of air pressure control without air damper travel time
t11
Air damper opening travel time
t12 Air damper in flow flame position (MIN) travel time
18...............t1
Permitted post-combustion time
6.................t16 Initial delay of consensus for air damper OPENING
7...............t0
Time up to automatic closure of programmer mechanism after burner start-up
NOTE: With voltages at 60 Hz, the times are reduced by about 20%.
54 / 107
0006080870_00709