2-5. Precautions for Installation in Heavy Snow
Areas
(1) The platform should be higher than the max. snow depth.
(Fig. 2-10)
(2) The 2 anchoring feet of the outdoor unit should be used for
the platform, and the platform should be installed beneath
the air intake side of outdoor unit.
(3) The platform foundation must be firm and the unit must be
secured with anchor bolts.
(4) In case of installation on a roof subject to strong wind,
countermeasures must be taken to prevent the unit from
being blown over.
2-6. Dimensions of Snow / Wind-proof Ducting and
Refrigerant Tubing Space for Installation
166
Min. 100
Outdoor
Unit
Duct
Air intake
About 1/2 of the unit height

3. HOW TO INSTALL THE INDOOR UNIT

■ 4-Way Air Discharge Semi-Concealed Type
(X, XM Types)

3-1. Preparation for Ceiling Suspension

This unit uses a drain pump. Use a carpenter's level to check
that the unit is level.

3-2. Mounting the Suspension Bolts

(1) Fix the suspension bolts securely to the ceiling using the
method shown in the diagrams (Figs. 3-1 and 3-2), by
attaching them to the ceiling support structure, or by any
other method that ensures that the unit will be securely and
safely suspended.
Duct
Outdoor Unit
Unit: mm
Duct
Higher than the maximum
snow depth
Air intake
Platform (foundation)
Hole-in-anchor
Hole-in-plug
(2) Follow Fig. 3-2 and Table 3-1 to make the holes in the
ceiling.
X Type
Min. 100
308
XM Type
Table 3-1 (X Type)
Length
Type
Fig. 2-11
18, 25,
36, 48
(3) Determine the pitch of the suspension bolts using the
supplied full-scale installation diagram. The diagram
and table (Fig. 3-3 and Table 3-2) show the relationship
between the positions of the suspension fitting, the unit,
and the panel.
X Type
Drain outlet
(other side) (VP25)
Suspension lug
17
Concrete
Suspension bolt (M10 or 3/8")
(field supply)
A (suspension bolt pitch)
C (ceiling opening dimension)
600
Ceiling opening dimensions
534
Suspension bolt pitch
A
B
788
723
Refrigerant tubing joint
(narrow side)
Insert
Fig. 3-1
Unit: mm
Fig. 3-2
Unit: mm
C
D
885
885
Refrigerant tubing joint
(wide side)