10-4. Items to Check Before the Test Run

(1) Turn the remote power switch ON at least 12 hours in
advance in order to energize the crank case heater.
(2) Fully open the closed valves on the liquid-tube and gas-
tube sides.

10-5. Test Run Using the Remote Controller

(1) Press and hold the remote controller
seconds or longer. Then press the
"TEST" appears in the LCD display during the test run.
Temperature control is not possible when test run mode
is engaged.
(This mode places a large load on the devices. Use it
only when performing the test run.)
(2) Use either Heating or Cooling mode to perform the test
run.
Note: The outdoor unit will not operate for approximately 3
minutes after the power is turned ON or after it stops
operating.
(3) If normal operation is not possible, a code appears on the
remote controller LCD display.
Refer to "10-7. Table of Self-Diagnostic Functions and
Corrections", and correct the problem.
(4) After the test run is completed, press the
Check that "TEST" disappears from the LCD display.
(This remote controller includes a function that cancels test
run mode after a 60-minute timer has elapsed, in order to
prevent continuous test run operation.)
(5) For the test run of an inverter outdoor unit, operate the
compressors for a minimum of 10 minutes (in order to
check for open phase).
* When performing a test run using a wired remote control-
ler, operation is possible without attaching the cassette-
type ceiling panel.
("P09" will not be displayed.)

10-6. Precautions

● Request that the customer be present when the test run is
performed. At this time, explain the operation manual and
have the customer perform the actual steps.
● Be sure to pass the manuals and warranty certificate to the
customer.
● Check that the 220 – 240 V AC power is not connected to
the inter-unit control wiring connector terminal.
button for 4
* If 220 – 240 V AC is accidentally applied, the indoor or out-
button.
Indoor unit control PCB
Varistor (black)
VA100
button again.
■ XM Type
Power PCB
Control PCB
Outdoor unit control PCB
8 – 10 HP
63PH (CN027, WHT)
FUSE (0.5A, F500)
EXCT
(CN030, RED)
RC P
(CN039, RED)
FUSE
(6.3A, F101)
CTL2
(CN202, GRN)
CTL1
(CN203, GRN)
R.C.ADD. Rotary switch
59
door unit control PCB fuse will blow in order to protect the
PCB. Correct the wiring connections, then disconnect the
2P connectors that are connected to the PCB, and replace
them with 2P connectors.
If operation is still not possible after changing the brown con-
nectors, try cutting the varistor.
(Be sure to turn the power OFF before performing this work.)
CHK (2P plug)
Fuse 0.5A
CHK (2P plug)
JP003
OC (CN500, BLU)
EMG (CN502, BRN)
IC002
N . P . C H E C K
LED2
(CN046, RED)
LED1
MODE (CN038)
IC001
2P connector (brown)
2P connector (blue)
Fuse 5A
2P connector (brown)
2P connector (blue)
SILENT (CN037, WHT)
PUMP DOWN (CN048)
TEMINAL (CN205, BLK)
C2 (CN020, WHT)
C1 (CN021, WHT)
TS (CN022, RED)
TO (CN023, BLK)
TD (CN024, BLK)
MOV1
(CN300, WHT)
MOV2
(CN301, BLK)
LED (D041)
EEPROM
TEST (CN033, RED)
C-CHK (CN035)
A.ADD (CN047)
R.C.ADD. DIP switch
D115
Fig. 10-4

Hide quick links:

Tabla de contenido
loading

Este manual también es adecuado para:

Spw-c906vh8

Tabla de contenido