Table 1-7 (Concealed-Duct High Static Pressure D Type)
Part Name
Figure
Special washer
Flare insulator
Drain socket
70
type
Tube
connector
90
type
* Used with the SPW-0705H8 outdoor unit
Table 1-8 (Outdoor Unit)
Name
Reducing Joint Tube
(ø19.05 → ø25.4)
Joint Tube (ø19.05)
Q'ty
Remarks
For suspending indoor
8
unit from ceiling
For gas and liquid
2
tubes
For drain pipe
1
connection
For decreasing size
1
of liquid tube from
ø12.7 to ø9.52 mm
For increasing size of
gas tube from ø25.4
1
to ø28.58 mm (Not
used)*
Figure
Q'ty
1
1

1-5. Tubing Size

(A) Single type
● During tubing work, try to make both the tubing length (L)
and the difference in elevation (H1) as short as possible.
Refer to Table 1-9.
Single
Table 1-9 Tubing Data for Models (Single)
Tubing Data
Liquid tube
Tubing size
outer diameter
Gas tube
Limit of tubing length (L)
Outdoor unit is
placed
Height
higher
Differential of
Indoor/Outdoor
Outdoor unit is
Units (H1)
placed
lower
Max. allowable tubing length at
shipment
Required additional refrigerant
Refrigerant charged at shipment
No additional charge of compressor oil is necessary.
* If the total tubing length exceeds 30 m, charge the amount of refrigerant
as shown above in "Required additional refrigerant" for every 1 m in
excess of 30 m for outdoor units.
9
Main tubing L
Models
SPW-C706VH8
SPW-C906VH8
9.52 (3/8)
mm (in.)
25.4
mm (in.)
(m)
100
30
(m)
30
(m)
5 – 30
(m)
40 *
(g/m)
5.3
(kg)
12.7 (1/2)
80 *
6.5