■ XM Type (for Link Wiring)

10-27. Caution

This unit may be used in a single-type refrigerant system
where 1 outdoor unit is connected to 1 indoor unit, and
also in a system where 1 outdoor unit is connected to
multiple indoor units (maximum 4 < Double-Twin >).
● This test run explanation describes primarily the procedure
when using the wired remote controller.
● If link wiring is used, set the outdoor unit system address
to allow the combination of indoor and outdoor units to be
identified. At the same time, indicate the indoor-outdoor unit
combination number in a location where it can be checked
easily (near the indoor unit nameplates). (This number will be
required for subsequent maintenance. Refer to 10-32-2, -3, -4.)
● Request that the customer be present when the test run is
performed. At this time, explain the operation manual and
have the customer perform the actual steps.
● Be sure to pass the manuals and warranty certificate to the
customer.
● Check that the 220 – 240 V AC wiring is not connected to the
inter-unit control wiring connector terminal.
If 220 – 240 V AC is accidentally applied, the indoor or
outdoor unit control PCB fuse will blow in order to protect the
PCB. Correct the wiring connections, then disconnect the 2P
connectors (blue, OC) that are connected to the PCB, and
replace them with 2P connectors (brown, EMG). (Refer to
the figure 10-27.)
If operation is still not possible after changing the brown
connectors, cut the JP003 for the indoor unit, and cut the
JP007 for the outdoor unit.
(Be sure to turn the power OFF before performing this work.)
Indoor unit control PCB
Power PCB
Control PCB
CHK(2P plug)
Outdoor unit control PCB
OC (CN500, BLU)
63PH (CN027, WHT)
FUSE (0.5A, F500)
EXCT
(CN030, RED)
RC P
(CN039, RED)
IC002
FUSE
(6.3A, F101)
CTL2
(CN202, GRN)
CTL1
(CN203, GRN)
N . P . C H E C K
LED2
(CN046, RED)
R.C.ADD. Rotary switch
MODE (CN038)
Fuse 5A
2P connector (brown)
JP003
2P connector (blue)
EMG (CN502, BRN)
SILENT (CN037, WHT)
PUMP DOWN (CN048)
TEMINAL (CN205, BLK)
C2 (CN020, WHT)
C1 (CN021, WHT)
TS (CN022, RED)
TO (CN023, BLK)
TD (CN024, BLK)
MOV1
(CN300, WHT)
MOV2
(CN301, BLK)
LED (D041)
EEPROM
TEST (CN033, RED)
LED1
C-CHK (CN035)
A.ADD (CN047)
R.C.ADD. DIP switch
IC001
D115

10-28. Test Run Procedure

Turn ON the
indoor and
outdoor power.
Automatic
Address
Fig. 10-27
81
Recheck the items to check
before the test run.
Check the combination (wiring) of
indoor and outdoor units.
YES
Is system "single-type"?
NO
Is group control with multiple
outdoor units used?
YES
(See 10-32-2) How to Set the
Outdoor Unit System Address
Set the outdoor unit system
address.
(See 10-32-1) How to Set
Automatic Address
Set the automatic address
setting from outside unit or
remote controller.
(*) Indicate (mark) the combination number. (See 10-32-3, -4)
Turn ON the indoor and outdoor power.
Set the remote controller to
"test run".
Can
operation be
started?
YES
Return the remote controller
to normal control.
(See 10-29)
(See 10-32-1)
NO
Automatic Address
(See 10-30)
(See 10-31)
NO
Refer to "Table of
Self-Diagnostic
Functions" to check
the system.
In addition, refer to
10-32 and correct any
items that need to be
corrected.
Note: Check the indoor-
side drainage.
(*) Required for
simultaneous-operation
multi systems and for
group control.
Fig. 10-28