PIPE TABLE FOR BURNER MOD. BT 120 DSN 4T WITH 5° E FUEL
AT 50° C (40° E AT PUMPING TEMPERATURE 5° C)
PUMP AXIS
PUMP AXIS
PUMP AXIS
GRAVITY FEED SYSTEM
1- Tank
2- Feed pipe
3- Mesh filter
4- Pump
GRAVITY SYSTEM WITH FEED FROM THE TOP OF THE TANK
1- Tank
3- Mesh filter
4- Pump
6- Intake pipe
INTAKE SUPPLY SYSTEM
Note For any components missing in the pipes, comply with current regulations.
H
Difference in level between min. level in tank and pump axis.
L
Total length of each pipe including the vertical section
Deduct 0.25 m for each elbow or gate.
12 / 40
0006081310_201211
5- Degassifier
6- Intake pipe
7- Burner return pipe
8- Automatic shut-off device with burner off
9 - Non-return valve
7- Return pipe
8- Automatic shut-off device with burner off
9 - Non-return valve
10- Foot valve
Maximum pressure at intake and return = 1 bar
Dimension P = 3.5 m (max)
1- Tank
3- Mesh filter
4- Pump
6- Intake pipe
7- Return pipe
10- Foot valve
H me-
L Total in me-
ters
ters
Ø = 1"¼
1
45
1.5
45
2
50
2.5
50
Maximum pressure at
intake and return = 1 bar
H me-
L Total in me-
ters
ters
Ø = 1"¼
1
45
1.5
45
2
50
2.5
50
H
L Total in meters
meters
Ø = 1"¼
Ø 1" ½
0.5
35
40
1
30
35
1.5
26
35
2
13
25
2.5
5
10
3
-
-
3.5
-
-