baltur GI MIST DSPGM Serie Manual De Instrucciones página 24

Quemadores mixtos gas / gasóleo de dos etapas progresivos / modulantes
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

To check the UV photocell and lock, proceed as follows:
- Start the burner.
- After at least one minute from ignition remove the UV photocell
from its seat and simulate a flame failure by covering it with
a dark cloth. The burner flame must turn off, the equipment
must repeat the ignition phase from the beginning and shut
down as soon as the flame turns on.
- The equipment can only be released manually by pressing
the release button. The burner shutdown efficiency test must
be performed at least twice.
Check that the boiler thermostats or pressure switches are
operating correctly (they must cause the boiler to shut down
when they intervene).
22 / 44
0006080103_201309
Tabla de contenido
loading

Este manual también es adecuado para:

Gi mist 350 dspgmGi mist 420 dspgmGi mist 510 dspgm

Tabla de contenido