Parameter Summary - KEB COMBIVERT F5 Serie Manual De Instrucciones

Ocultar thumbs Ver también para COMBIVERT F5 Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 143

2.2 Parameter Summary

Display Parameter
CP. 0
Password input
CP. 1
Actual frequency display
CP. 2
Set frequency display
CP. 3
Inverter status display
CP. 4
Apparent current
CP. 5
Apparent current / Peak value
CP. 6
Utilization
CP. 7
Intermediate circuit voltage
CP. 8
Intermediate circuit voltage/
Peak value
CP. 9
Output voltage
CP.10
Minimal frequency
CP.11
Maximal frequency
CP.12
Acceleration time
CP.13
Deceleration time(-0,01 see CP.12)
CP.14
S-curve time
CP.15
Boost
CP.16
Rated frequency
CP.17
1)
Voltage stabilization
1)
CP.18
Carrier frequency
CP.19
Step frequency 1
CP.20
Step frequency 2
CP.21
Step frequency 3
1)
CP.22
DC-braking / Mode
CP.23
DC-braking / Time
CP.24
Max. ramp current
CP.25
Max. constant current
1)
CP.26
Speed search condition
CP.27
Quick stop time
CP.28
Reaction of ext. overtemperature
1)
CP.29
Analog output 1 / Function
CP.30
Analog output 1 / Amplification
CP.31
1)
Relay output 1 / Function
1)
CP.32
Relay output 2 / Function
CP.33
Relay output 2 / Switching level
CP.34
1)
Source of rotation direction
CP.35
1)
AN1 interface selection
CP.36
AN1 zero point hysteresis
1)
Enter-Parameter
2)
depending on power circuit
Operation of the Unit
Setting range
Resolution Factory setting
0...9999
1
0,0125 Hz
0,0125 Hz
0,1 A
0,1 A
1 %
1 V
1 V
1 V
0...400 Hz
0,0125 Hz
0...400 Hz
0,0125 Hz
0,00...300,00 s
0,01 s
0,01 s
-0,01; 0,00...300,00 s
0,00 (off)...5,00 s
0,01 s
0,0...25,5 %
0,1 %
0...400 Hz
0,0125 Hz
1...650 V (off)
1 V
2)
2/4/8/12/16 kHz
-400...400 Hz
0,0125 Hz
-400...400 Hz
0,0125 Hz
-400...400 Hz
0,0125 Hz
0...9
1
0,00...100,00 s
0,01 s
0...200 %
1 %
0...200 % (off)
1 %
0...15
1
0,00...300,00 s
0,01 s
0...7
1
0...12 (0...21)
1
-20,00...20,00
0,01
0...78
1
0...78
1
0,01
-30000,00...30000,00
0...9
1
0...2
1
-10,0...10,0 %
0,1 %
0 Hz
GB
70 Hz
5,00 s
5,00 s
0,00 s (off)
2,0 %
50 Hz
650 (off)
2)
5 Hz
50 Hz
70 Hz
7
10,00 s
140 %
200 % (off)
8
2,00 s
7
2
1,00
4
27
4,00
2
0
0,2 %
GB - 11

Hide quick links:

Tabla de contenido
loading

Este manual también es adecuado para:

Combivert f5 compactCombivert f5 generalCombivert f5 basic

Tabla de contenido