Initial load auger 2
Description
Setting this function allows activation of gearmotor operation relevant to the supplementary
hopper for a fixed time. It starts with button P1 and stops with button P4.
6.2.3. MENU 03 - USER SETTING
With this menu it is possible to carry out the following settings:
Language
Description
With this selection it is possible to select the dialogue language from those available entered
in the menu, and namely: ITALIAN - FRENCH - ENGLISH - GERMAN – SPANISH.
Buzzer
Description
With this selection it is possible to activate/deactivate boiler acoustic signalling.
Lighting
Description
With this selection it is possible to change the brightness of the backlit display from a
minimum of 0 to a maximum of 100.
Heating Delta
Description
With this selection, it is possible to set:
▪ the range between the SET temperature and the actual boiler shutdown temperature;
▪ the range between the SET temperature and the actual boiler relighting temperature.
This range can be set from a min. of 0.5°C to a max. of 20°C depending on the customer's
needs and/or the type of system.
Boiler/Puffer Delta
Description
With this selection, it is possible to set:
▪ the range between the SET temperature and the actual boiler relighting temperature.
This range goes from a min. of 0.5°C to a max. of 20°C depending on the customer's needs
and/or the type of system.
Pellet level
Description
With the selection set to ON, the no pellets signal can be managed with:
▪ a message on the panel "NO PELLETS";
▪ management of a supplementary pellet hopper (available on request).
With the selection OFF, the possible supplementary hopper is disabled and no message
appears on the panel.