Disable - Bentel Security FC500 Manual Del Usuario

Analgicas contraincendios
Ocultar thumbs Ver también para FC500:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

To access the DISABLE menu from the main
"STANDBY" display, you will be asked to enter a "User
Code" password (the default code is 11111): each en-
tered digit will be hidden with the * symbol.
This activates the procedure used to enable/disable:
Display List of disabled devices, the loop devices (input
or output devices), the SW zones, the Outputs of control
panel, the network devices, the Telecom modules; , the
Conventional "on-board" zones;
+
When a device at least is disabled, the Disable
LED will be glowing, and any Alarm or Fault, rela-
ted to the disable device, will be ignored.
The disabled and enabled modes are as follows:
Input Devices A disabled input device (Detector,
Input module, Conventional Zone module, Addressable
Call-points) will not generate ALARM or FAULT status.
Ø To clear ALARM status generated by a input device -
RESET the fire control panel.
Output Devices ALARM or FAULT status will not acti-
vate disabled output devices (Output modules, Addres-
sable Sirens).
Ø To stop the output devices activated by FAULT sta-
tus - Disable the devices concerned.
Ø To stop the output devices activated by an ALARM
status - RESET the fire control panel.
+
Output devices enabled during ALARM or FAULT
status (programmed), will be activated immedia-
tely.
The Display in Figure 65 show how to select the devi-
ces to Disable/Enable.
In this phase:
Alphanumeric keypad Use the Alphanumeric keypad
to select the Disable/Enable options.
Use the 1 key to select the Disab. List (see Figure 65).
Use the 2 key to select the Disabled option of Loop de-
vices.
Use the 3 key to select the Disabled option of SW zo-
nes.
Use the 4 key to select the Disabled option of Outputs.
Use the 5 key to select the Disabled option of device in
the Network;
Use the 6 key to select the Disabled option of Telecom
52
modules;
Use the 7 key to select the Disabled option of Conv.
Zone on board.
Cursor Keys No function is related to UP Key;
No function is related to Down Key;
No function is related to Right Key;
No function is related to Left Key.
ESC Key Use ESC key to cancel the operation and to
step back to previous page.
ENTER key No function is related to ENTER key.
Function Keys No function is related to F1 key;
No function is related to F2 key;
No function is related to F3 key;
No function is related to F4 Key.
Control Panel name
Master control panel
1=Dis. list
4=Output
7=Conv.zone
Options
Figure 65 Display DISABLE menu
Analogue Fire Panels

DISABLE

This symbol shows the
presence of the connection
Control panel
Status
between the User Interface
Access Level
and the Main Board
lev.2: DISABLE
2=devices
3=SW zone
5=Network
6=Telecom
FC500
Tabla de contenido