Signalling; The Status Leds; Important; Day/Night Mode - Bentel Security FC500 Manual Del Usuario

Analgicas contraincendios
Ocultar thumbs Ver también para FC500:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Signalling

The system status is indicated by the
- control panel LEDs;
- back-lighted display (40 characters on 4 lines);
- buzzer.
n The status LEDs
The following section describes how the Control panel
LEDs operate, and the actions that can be taken during
the various phases signalled on the LEDs. During
standby status,ONLY the GREEN Mains LED and the
Day mode LED (if the control panel is in Day mode)
should be On (glowing).
+
The two FAULT LEDs slow blinking ONLY indi-
cates a FAULT event in memory.
LEDs
FIRE Glowing indicates Alarm status. In the event of an Alarm, the Control panel will activate the
unbypassed alarm outputs.
More Alarms Glowing indicates more Alarm status.
Pre-alarms Blinking indicates Pre-alarm status.
Communicator
Glowing indicates that transmission was successful.
(Red)
Blinking indicates that transmission is in progress. On the display of the control panel it is possi-
ble to know the connection type: PSTN, GSM, or LAN network.
FAULT Glowing indicates the presence of a Fault: the following LEDs or the screen on the display indicate
the type of the Fault. Slow blinking indicates a fault event in memory (Reset turns OFF ).
Logic Unit Glowing indicates a blocked Control panel. IMPORTANT: Maintenance required.
NOTE – When the Control panel is switched on for the first time, this LED will blink until a Reset has
been performed.
Lost Device Glowing indicates that a Loop device has disappeared (missing address).
Communicator
Glowing indicates the Dialer has been disabled; Slow blinking indicates that the dialer has broken
(Amber)
down
Nac Fire
Glowing indicates that NAC FIRE Output is bypassable (Disabled), Slow blinking indicates the
Output
presence of a Fault on NACFIRE Output.
Earth Glowing indicates a Voltage leakage to Earth.
IMPORTANT: Check wiring insulation
Low Battery Glowing indicates Batteries empty or faulty. If this condition persists, the batteries will be unable to
function as intended in the event of blackout, IMPORTANT: New batteries required.
NO Battery Glowing indicates Batteries empty or disconnected ; check if the connections are correct.
MAINS
Glowing indicates Mains failure (230 V) or Switching Power supply fault. During this condition,
(amber)
the Control panel will be powered by the batteries.
Day mode Glowing indicates that the Control panel is operating in Day Mode
OFF indicates that the Control panel is operating in Night Mode
Disabled Glowing indicates the Disabled status of any bypassable entity..
Silence Glowing indicates that Silenceable outputs have been forced to standby by means of SILENCE key;
in Day Mode the SILENCE will remain until the SILENCE key will not be pressed again,
while in Night Mode after the Silence Time expires automatically the SILENCE will end.
Test Glowing indicates Test conditions on at least one zone.
MAINS
OFF indicates Mains failure (230 V).
(Green)
IMPORTANT: Power must be restored before the batteries empty.
Table 4 Description of the status LEDs
:
DESCRIPTION
- ENGLISH - INTRODUCTION
n Day/Night Mode
The control panel can operate in DAY or NIGHT Mode.
If the system is silenced during DAY Mode, SILENCE
status will be held until the system is unsilenced (i.e. un-
less new alarms or faults occur). If the system is silen-
ced during NIGHT Mode, SILENCE status will be held
until the Night Mode Silence time expires (refer to "Si-
lence" ). On power up (at default) the system will set to
DAY Mode. During this operating mode, silenced
alarms/faults will not be unsilenced automatically.
+
This Control panel will generate an Instant Alarm if
alarm conditions are detected during Night Mode
or if an alarm is triggered from a Callpoint.
35
Tabla de contenido
loading