APPLICATION OF THE BURNER TO BOILER

REMARKS
The burner's head penetration depth, into the boiler's combustion chamber, must be specified by the boiler's manufacturer.
The burner is correctly fitted if the preheating tank is slightly tilted (i.e. higher on the fuel outlet side towards the nozzle).
This slight tilt prevents any build-up of gas inside the tank.
The presence of gas inside the preheating tank will considerably lengthen the time required to get the fuel up to pressure. Therefore the
burner could easily lock-out. When fitting the burner to the boiler make sure that it is not positioned in a way that cancels out this tilt or,
even worse, that the preheater is tilted the opposite way.
10 / 38
0006080547_201610
1 - Boiler plate
2 - Insulating gasket
3 - Burner fixing flange
4 - Stud bolt
5 - Locking nut with washer