ENG
2.5
Specific fastening instructions
Triango 100 W
Fastening material is not included with delivery.
The ceiling mounting must only be mounted on ceilings
having a concrete stability class B25 (C20/25) or higher.
Solid ceiling reinforcement parts must not come into contact
with the ceiling mounting. If there is any doubt, an authorized
professional must confirm that mounting is possible on the
mounting base being used. The load-bearing capacity of the
ceiling construction must be planned, checked and confirmed
by a structural engineer beforehand.
Borings must be made by specialists in compliance with the
boring tolerances for the reinforcement anchor that have
been approved by the manufacturer. In the event of faulty
drilling, such as drilling through a metal support bar, a
structural engineer must be called in.
The luminaire should be installed in such a way as to avoid
permanent strain on the height stops during operation.
If there is plastering or cladding over the concrete, make sure
the fixing anchor is properly attached right into the concrete.
Screws must be tightened carefully using a torque wrench
that complies with the instructions of the mounting element
manufacturer.
Triango 100 W
Fastening material is not included with delivery.
The luminaire must only be mounted on walls that can
guarantee a secure hold. Specialist staff will find details of
the requirements in Chapter 5.1 (Load data).
3.
INSTALLATION: Triango 100 C
3.1
Workload data
Bending moment M
B
Vertical weight F
G
3.2
Shortening the ceiling tube
►
Before shortening the ceiling tube, remove the cable
from the ceiling tube.
►
Use a hack saw to shorten the upper end of the ceiling
tube to the desired length, and then deburr it.
22
Remove the fastening screw "C".
►
Insert the ceiling tube "A" into the ceiling bracket "B" and
►
drill the ceiling holder's existing hole to 9 mm in diameter.
Drill the opposite hole separately.
►
Note: Pull the cable through from the lower side to the upper
pipe side (the 3-pin plug first) after sawing and drilling.
3.3. Installing the ceiling holder
Assembly by qualified personnel
►
Assembly must be done by qualified personnel only.
Lack of appropriate knowledge may pose a death
hazard.
►
Two people are needed for assembly.
Death hazard from falling luminaire.
►
The ceiling mount must only be mounted on ceilings
with a concrete stability class of B25 (C20/25) or
245 Nm
higher.
160 N
►
There should be no contact with reinforcement parts
of the solid ceiling during mounting. When in doubt, a
licensed technician must approve installation on the
specific installation surface. The load bearing capacity
of the ceiling structure must be planned, checked and
confirmed by a structural engineer beforehand.
►
The holes must be drilled by a professional and in
compliance with the drilling tolerances permitted by
the manufacturer of the fastening anchor. If a drilling
error occurs, such as drilling into a reinforcement bar,
a structural engineer must be consulted.
►
Install the luminaire such that the vertical stops are not
continuously stressed during operation.
►
With plaster or cladding in front of concrete, the
fastening anchor must be driven completely into the
concrete.
►
The screws must be tightened carefully using a torque
wrench according to the specifications of the fastening
anchor manufacturer.
Death hazard from electric shock.
►
All poles of the power cable must be disconnected
from the power grid from an external lockable switch.
A
B
DANGER
DANGER
DANGER
C