• Recording of fault protocol
• Electronic monitoring of the motor current
• Programmable turn-on-delay
• Programmable pump follow-up
• Programmable pump changeover interval
• Switchable service- and ATEX- mode
3.3 TECHNICAL DATA
OPERATING VOLTAGE
VOLTAGE OF CONTROL SYSTEM
POWER CONSUMPTION
PRESSURE RANGE
TURN-ON-DELAY
FOLLOW-UP TIME
RUNTIME MONITORING
FAULT PROTOCOL MEMORY
4. INSTALLATION
DISCONNECT THE SYSTEM BEFORE ANY INTERVENTION !
4.1 MECHANICAL FIXATION
The control system has to be fixed on an flat surface. In order to fasten the control system, the housing cover has to be opened.
4.2 MAINS CONNECTION
DANGER
Electrical connection work performed by an unqualified individual.
Risk of death by electric shock!
 All electrical connections are to be established by an authorised professional only.
 Settings and adjustments on the control system as well as the commissioning of the control system are to be
carried out by qualified persons only.
 The electrical connection must comply with the standards in force in the country where the appliance is
installed.
The left cable gland is intended for the cable entry of the mains cable. The separate cables are to be clamped into the termi-
nals in the manner described below. According to the motor which is used, a single-phase or a three-phase connection can be
established.
NOTICE
 The power supply has to be secured by an independent all-pole fuse which can be switched off (max.
20 A).
4.3 CONNECTION OF THE PUMP MOTOR
Either single-phase or three-phase motors may be connected according to the following connection diagrams.
230 V or 400 V AC
50-60 Hz
230 V AC
50-60 Hz
approx. 6 VA
0-1 mWs
0-180 sec
0-180 sec
0-300 sec
32 memory positions
• Internal pressure sensor
• Level indication in cm
• 4 digital inputs for thermostatic switch
• 4 digital inputs for floating switch or reed sensor
• 1 analogue input for transmitter 4-20mA
• 1 analogue pressure input 0-100(500) mBar
MAINTENANCE INTERVAL COUNTER
TURN-ON-DELAY 2 PUMPS
MOTOR CURRENT LIMITATION
OPERATING TEMPERATURE RANGE
DIMENSIONS
MAX. PRE-FUSE
POTENTIAL-FREE ALARM CONTACT
DEGREE OF PROTECTION
HOUSING
19
EN
0–365 days, adjustable
0-60 sec.
0.5-14 A
-20 - +60°C
180x180x90 mm
20 A
3 A max.
IP 65
Polycarbonate