Mitsubishi Electric TRANE CITY MULTI TPMFYP BM140 Serie Manual De Instalación página 11

Ocultar thumbs Ver también para TRANE CITY MULTI TPMFYP BM140 Serie:
Idiomas disponibles

Idiomas disponibles

6. Test run
Step 1 Switch the remote controller to "Test run".
1 Select "Service" from the Main menu, and press the [SELECT/HOLD] button.
2 When the Service menu is selected, a window will appear asking for the password. (Fig. 6-2)
To enter the current maintenance password (4 numerical digits), move the cursor to the digit you want to change with the
(0 through 9) with the
or
button. Then, press the [SELECT/HOLD] button.
F3
F4
Note: The initial maintenance password is "9999". Change the default password as necessary to prevent unauthorized access.
Have the password available for those who need it.
Note: If you forget your maintenance password, you can initialize the password to the default password "9999" by pressing and holding the
simultaneously for three seconds on the maintenance password setting screen.
3 Select "Test run" with the
or
F1
F2
4 Select "Test run" with the
or
F1
F2
Service menu
Enter maintenance password
Select: SELECT
Cursor
ON
RETURN SELECT
MENU
OFF
HOLD
Fig. 6-2
Step 2 ��������������������������������
1 Press the
button to go through the operation modes in the order of "Cool"
F1
and "Heat". (Fig. 6-5)
Cool mode: Check the cold air blow off.
Heat mode: Check the heat blow off.
Note:
Check the operation of the outdoor unit's fan.
2 Press the [SELECT/HOLD] button and open the Vane setting screen.
AUTO vane check
1 Check the auto vane with the
F1 F2
2 Press the [RETURN] button to return to "Test run operation".
3 Press the [ON/OFF] button.
button, and press the [SELECT/HOLD] button. (Fig. 6-3)
button, and press the [SELECT/HOLD] button. (Fig. 6-4)
Service menu
Test run
Input maintenace info.
Settings
Check
Others
Main menu: RETURN
Cursor
RETURN SELECT
MENU
HOLD
Fig. 6-3
buttons. (Fig. 6-6)
Test run menu
Test run
Drain pump test run
Service menu: MENU
Cursor
ON
RETURN SELECT
MENU
OFF
HOLD
Fig. 6-4
vane.
Test run
Remain
Pipe
Cool
Auto
Switch disp.
SELECT
Mode
RETURN SELECT
MENU
HOLD
Fig. 6-5
or
button, and set each number
F2
F1
and
F1
ON
OFF
Test run
Fan
Vane
ON
RETURN SELECT
MENU
OFF
Fig. 6-6
buttons
F2
Remain
ON
OFF
HOLD
en
10
loading