Mitsubishi Electric TRANE CITY MULTI TPMFYP BM140 Serie Manual De Instalación página 10

Ocultar thumbs Ver también para TRANE CITY MULTI TPMFYP BM140 Serie:
Idiomas disponibles

Idiomas disponibles

5. Electrical work
5.7. Electrical characteristics
Model
TPMFYP006BM140
TPMFYP008, 012BM140
TPMFYP015BM140
6. Test run
6.1. Before test run
► After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power sup-
ply or control wiring, wrong polarity, and no disconnection of 1 phase in
the supply.
► Use a 500-volt megohmmeter to check that the resistance between the
power supply terminals and ground is at least 1.0 MΩ.
Controller interface
MENU
4
Function buttons
7
en
9
Hz
Volts
60Hz
208 / 230V
ON
RETURN SELECT
HOLD
OFF
3
2
1
8
9
0
Fig. 6-1
Symbols: MCA: Max. Circuit Amps (= 1.25×FLA)
IFM: Indoor Fan Motor
Power supply
Voltage range
MCA (A)
0.25 / 0.25
198 to 253V
0.26 / 0.26
0.33 / 0.33
► Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0 MΩ.
6.2. Test run
The following 2 methods are available.
6.2.1. Using wired MA remote controller (Fig. 6-1)
▌1 [ON/OFF] button
Press to turn ON/OFF the indoor unit.
▌2 [SELECT/HOLD] button
Press to save the setting.
When the Main menu is displayed, pressing this button will enable/disable the
5
HOLD function.
▌3 [RETURN] button
Press to return to the previous screen.
▌4 [MENU] button
Press to bring up the Main menu.
▌5 Backlit LCD
Operation settings will appear.
6
When the backlight is off, pressing any button turns the backlight on and it will
stay lit for a certain period of time depending on the screen.
When the backlight is off, pressing any button turns the backlight on and does
not perform its function. (except for the [ON/OFF] button)
▌6 ON/OFF lamp
This lamp lights up in green while the unit is in operation. It blinks while the
remote controller is starting up or when there is an error.
▌7 Function button [F1]
Main display: Press to change the operation mode.
Menu screen: The button function varies with the screen.
▌8 Function button [F2]
Main display: Press to decrease temperature.
Main menu: Press to move the cursor left.
Menu screen: The button function varies with the screen.
▌9 Function button [F3]
Main display: Press to increase temperature.
Main menu: Press to move the cursor right.
Menu screen: The button function varies with the screen.
▌0 Function button [F4]
Main display: Press to change the fan speed.
Menu screen: The button function varies with the screen.
FLA: Full Load Amps
Output: Fan motor rated output
IFM
Output (kW)
FLA (A)
0.028 / 0.028
0.20 / 0.20
0.028 / 0.028
0.21 / 0.21
0.028 / 0.028
0.26 / 0.26