Keypad (HMI) and Basic Programming
P1016 - Multispeed Reference 6
Adjustable
0 to 18000 rpm
Range:
Properties:
-
Access Groups
SPLC
via HMI:
Description:
Sets the speed reference 6 for the Multispeed application.
P1017 - Multispeed Reference 7
Adjustable
0 to 18000 rpm
Range:
Properties:
-
Access Groups
SPLC
via HMI:
Description:
Sets the speed reference 7 for the Multispeed application.
P1018 - Multispeed Reference 8
Adjustable
0 to 18000 rpm
Range:
Properties:
-
Access Groups
SPLC
via HMI:
Description:
Sets the speed reference 8 for the Multispeed application.
4.2.4 3-Wire Start/Stop Command Application
The CFW700 has the 3-Wire Start/Stop application that allows the inverter Start/Stop command
to be performed as a direct online start with emergency button and retention contact.
This way, the digital input (DIx) programmed to "Function 1 of the Application (Start)" will be able
to enable the inverter with a single pulse in case the DIx set to "Function 2 of the Application
(Stop)" is active. The inverter disables the ramp when the digital input Stop is inactive. The
picture below show how it works.
44 | CFW700
Factory
1500 rpm
Setting:
Factory
1800 rpm
Setting:
Factory
1650 rpm
Setting: