Operation
30
Pin no.
Description
1
Input
Analog speed
setpoint setting
via control volt-
age
2
Input
UART
3
GND
4
Output
UART
5
Input
PWM speed set-
point setting
6
Input
Remote ON/OFF
7
Output
Error signal
If no supply voltage is present, the inputs must be potential-
free!
Tab.13: Assignment of control cable connection
7.4 Speed specification
The pump can be actuated by analog or digital means. The
speed setpoint of the pump can be carried out by one of three
options:
à
Analog control voltage,
à
PWM setpoint setting,
à
Digital setpoint setting.
A standard-analog configured pump can be switched to digital
mode at any time with the start command "dU" via the UART
interface. The pump then remains in this mode until it is ac-
tively disconnected from the supply voltage.
Translation of Original Operating and Installation Instruction, KNF
Diaphragm pump N952KTE-W N952KT.29E-W
Level / state
0...5 V
Tx
0V
Rx
LVTTL
1...99%
100 Hz-5 kHz
High = Off
Low = On
Error = high
No error = low
339866-336533 02/23