AL probe 1
The temperature of the AL function is measured on this sensor.
AL sensor 2
Optional AL sensor
If this sensor is set, for a correct heating AL Tset must also be reached in this sensor for the
disinfection time.
AL-Times
AL heating is attempted during these time intervals. If, in the defined period, the condition-AL is
met (Tref in the probes defined for the disinfection time period), the heating is completed and
recorded as "AL last heating".
Heat transfer
With this function, the energy from one storage can be loaded into another.
Transfer
Activate the function
Transfer Tmin
Minimum temperature in the source storage for heat transfer.
Δt transfer on
Temperature differential for transfer. If the temperature differential between the receptor and
heat source sensors exceeds "DT transfer on ", the relay is switched on. If the temperature
differential between the receptor and heat source sensors reaches or becomes smaller than
transfer off, the relay is switched off.
Max temp.
If this temperature is measured on the sensor in the target storage, the relay will be switched
off.
Heat source
Set the probe placed in the storage from which the energy is extracted.
Receptor
Set the probe placed in the storage where the energy is transferred.
168
EN
code 3542A420 - Rev. 00 - 12/2021
ECOTRONIC HiTech
Δt