Appendix 1: Technical Specifications - Tripp-Lite SRCOOL60KCW El Manual Del Propietario

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Appendix 1: Technical Specifications

Model
Phase/ Frequency/ Input Voltage
Max. Power Consumption
Rated Cooling Capacity *
Max. Cooling Capacity **
Air Volume
Rated Chilled Water Flow Rate
Pressure Drop
Drain Pump (Optional)
Display
Max. Return Air Temperature
Max. Water Inlet Temperature and Pressure
Operational Audible Noise
Operating Temperature
Storage Temperature
Dimensions [Width x Depth x Height]
Net Weight
Notes:
1. Refer to the unit's rating label for the safety rating.
2. All specifications are subject to change without prior notice.
* Testing conditions for rated cooling capacity:
Return air temperature: 40.6°C DB/ 21.6°C WB/ chilled water inlet temperature degree: 7°C/ chilled water outlet temperature degree: 15.8°C.
** Testing conditions for the maximum cooling capacity:
Return air temperature 48.9°C DB/ 23.9°C WB/ chilled water inlet temperature: 7°C/ chilled water outlet temperature: 15.4°C.
SRCOOL60KCW
1~, 50/60 Hz, 208-230V ± 10%
2.41 kW
43.4 kW
59.1 kW
7500m³/h (264,860 ft.
80 Lpm (17.6 gal./min.)
98 kPa
Flow rate: 5 L/h (1.3 gal./hr); Rated vertical lift: 5 m (16 ft.)
HMI: LCD 64 x 128 pixels and four LED indicators
50°C (122°F)
22°C (72°F), 5 kg/cm
88 dBA @ 4,400 CFM
4 ~ 50°C (39 ~ 122°F); 30 ~ 85% RH, non-condensing
-15 ~ 65°C (59 ~ 149°F); 0 ~ 95% RH, non-condensing
300 x 1090 x 2000 mm (12 x 43 x 79 in.)
187 kg (412 lb.)
56
3
/hr.)
2
Tabla de contenido
loading

Tabla de contenido